1MRS755769
Voltage Relay
Technical Reference Manual
Table 7.-2 Setting group 2 (Continued)
Variable
Resetting time of stage U<
Drop-off/pick-up ratio D/P<
Start value of stage U<<
Start value of stage U
<
1
Operate time of stage U<<
IDMT operation mode setting for
stage U<<
IDMT time multiplier, k<<
Start value of stage U
>
0
Operate time of stage U
>
0
Resetting time of stage U
0
Start value of stage U
>>
0
Operate time of stage U
>>
0
Predefined time of CBFP
Checksum, SGF1
Checksum, SGF2
Checksum, SGF3
Checksum, SGF4
Checksum, SGF5
Checksum, SGB1
Checksum, SGB2
Checksum, SGB3
Checksum, SGB4
Checksum, SGB5
Checksum, SGR1
Checksum, SGR2
Checksum, SGR3
Checksum, SGR4
Checksum, SGR5
Checksum, SGR6
Checksum, SGR7
Checksum, SGR8
Checksum, SGL1
Checksum, SGL2
Checksum, SGL3
Checksum, SGL4
Checksum, SGL5
Checksum, SGL6
Checksum, SGL7
Checksum, SGL8
Group/
Setting range
Channel 2
(R, P)
2S17
0.07...60.0 s
2S18
1.01...1.05
2S19
0.20...1.20 × U
2S20
0.20...1.20 × U
2S21
0.10...600 s
2S22
0...1
2S23
0.10...2.00
2S24
2.0...80.0% U
2S25
0.10...600 s
>
2S26
0.07...60.0 s
2S27
2.0...80.0% U
2S28
0.10...600 s
2S29
0.10...60.0 s
2S61
0...255
2S62
0...4095
2S63
0...15
2S64
0...1023
2S65
0...255
2S71
0...32767
2S72
0...32767
2S73
0...32767
2S74
0...32767
2S75
0...32767
2S81
0...8191
2S82
0...8191
2S83
0...8191
2S84
0...8191
2S85
0...8191
2S86
0...8191
2S87
0...8191
2S88
0...8191
2S91
0...16383
2S92
0...16383
2S93
0...16383
2S94
0...16383
2S95
0...16383
2S96
0...16383
2S97
0...16383
2S98
0...16383
REU 610
Default
Customer's
setting
setting
0.07 s
1.03
0.20 × U
n
n
0.20 × U
n
n
0.10 s
0
0.10
2.0% U
n
n
0.10 s
0.07 s
2.0% U
n
n
0.10 s
0.10 s
0
2730
0
128
0
0
0
0
0
0
2730
2730
2730
1365
1365
0
0
0
0
0
0
0
0
0
0
0
127

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents