7.1 GENERAL

While Sullair has built into this compressor a com-
prehensive array of controls and indicators to as-
sure you that it is operating properly, you will want
to recognize and interpret the reading which will
call for service or indicate the beginning of a mal-
function. Before starting your Sullair compressor,
read this section thoroughly and familiarize your-
self with the controls and indicators --- their pur-
pose, location and use.

7.2 STANDARD PARAMETER SETUP

Pressing the program key enters parameter dis-
play and edit mode. To move to the next parameter
press the program key. To increment a parameter
press the up arrow key or logo key. The logo key
will increment by 10. To decrement the value press
the down arrow key.
The parameters are displayed in the following or-
der:
S Unload pressure --- The pressure where
the machine is unloaded. For example if
this parameter is set to 110 psi the machine
will unload when the line pressure is above
110 psi.
UNLOAD
100 PSI
S Load differential --- The pressure differ-
ential below the unload pressure where the
machine is loaded. For example, if the un-
load pressure is set to 110 and the load dif-
ferential is set to 10, the machine will load
when the line pressure goes below 100
psi.
LOAD
10 PSI
S P1 Max --- Maximum sump pressure. An
alarm and shut down will occur when the
sump pressure rises above this pressure.
P1 MAX
135 PSI
S Wye to delta transition timer --- For full
voltage starters this parameter is set to 0.
WYE DELT
10 SEC
S Restart time --- Time to wait after power up
before starting machine. This parameter is
used to keep several machines from start-
ing at the same time after power up, or to
delay start until other equipment is started.
If disabled the machine will not automati-
COMPRESSOR OPERATION
cally start after power up.
RST TIME
10 SEC
S Unload Stop Timer --- If the machine is
running in AUTO mode, this parameter
specifies the amount of time that the ma-
chine will run unloaded before shutting off.
If the time is set less than 15 minutes (for
example five minutes), there may be times
when the machine will run unloaded for
more than five minutes. This is because
there is another timer that keeps the ma-
chine from being started more than four
times an hour.
UNLD TIM
15 MIN
S Language select --- English, German,
Spanish, Italian and French may be se-
lected for display language.
LANGUAGE
ENGLISH
S Units --- English or metric units may be se-
lected.
UNITS
ENGLISH
S Communications ID # --- This is the net-
work address of a machine. If there is more
than one machine connected to the net-
work, each machine must have a unique
number.
COM ID #
S Communications baud rate --- This
should always be selected to 9600 baud
for all sequencing modes. It may be lower
for slave or monitoring modes.
BAUDRATE

7.3 DELUXE PARAMETER SETUP

The following parameters are only available on de-
luxe model Supervisor II.
S Sequence method --- This parameter sets
the method used for sequencing. The
choices are DISABLED, REMOTE, SLAVE,
HOURS, COM ID#. See the Sequencing &
Section 7