Circutor CVM-E3-MINI Instruction Manual page 77

Power analyzer
Hide thumbs Also See for CVM-E3-MINI:
Table of Contents

Advertisement

CVM-E3-MINI
Bit 7
0
7�3�7�13� Communications
Configuration variable
Protocol
Modbus and BACnet: Peripheral number
Modbus : Baud rate
Modbus : Parity
Modbus : Data bits
Modbus : Stop bits
BACnet: Device ID
BAcnet: MAC
BAcnet: Baud rate
7.3.7.14. Password configuration
These variables allow you to lock or unlock access to the programming menu, and also allow
you to change the password code. The password code may only be changed through this com-
mand.
The device does not need you to enter the old password in order for it to record the new one; it
records the new one directly without any verification.
Password
Configuration variable
Password value
(6)
Lock-Unlock
The password value is read and written in hexadecimal.
(6)
Instruction Manual
Table 45:Variable format: Status of the digital outputs�
Bit 6
Bit 5
Bit 4
Bit 3
0
0
0
Table 46:Modbus memory map: Communications
Communications
2EE0- 2EE1
Table 47:Modbus memory map: Password configuration
Address
2B70
2B71
Bit 2
Bit 1
0
0
0
Address
Valid data margin
0 : Modbus
2742
1: Bacnet
2743
0 - 255
0: 9600 - 1:19200 - 2:38400
2744
3:57600
0: No parity
2745
1: Odd parity
2: Even parity
0 : 8 bits
2746
1: 7 bits
0 : 1 stop bit
2747
1: 2 stop bits
0- 99999
2EE2
2744
0: 9600 - 1:19200 - 2:38400
Valid data margin
0 - 9999
0: Unlock
1: Lock
Bit 0
Output 1
0: OFF
1: ON
Default
value
0
1
0
0
0
0
2
0- 127
1
1
Default value
1234
0
77