Electrical Installation
4.8 Control Wiring
4.8.1 Control Terminal Types
Illustration 4.9 shows the removable frequency converter
connectors. Terminal functions and default settings are
summarized in Table 4.1 and Table 4.2.
1
2
3
Illustration 4.9 Control Terminal Locations
1
37 38 12 13 18 19 27 29 32 33
Illustration 4.10 Terminal Numbers
See chapter 9.6 Control Input/Output and Control Data for
terminal ratings details.
Terminal
Parameter
Digital I/O, pulse I/O, encoder
12, 13
–
+24 V DC
Parameter 5-10
18
Terminal 18
[8] Start
Digital Input
Parameter 5-11
19
Terminal 19
[10] Reversing
Digital Input
MG07A402
Operating Guide
2
61
68 69
3
42 53 54 50 55
Default
Description
setting
24 V DC supply
voltage. Maximum
output current is
100 mA for all
24 V loads.
Digital inputs.
Danfoss A/S © 10/2017 All rights reserved.
Terminal
Parameter
Parameter 5-01
Terminal 27
Mode
Parameter 5-12
27
Terminal 27
Digital Input
DI [2] Coast
Parameter 5-30
inverse
Terminal 27
DO [0] No
Digital Output
operation
Parameter 5-13
[14] Jog
29
Terminal 29
Digital Input
Parameter 5-14
[0] No
32
Terminal 32
operation
Digital Input
Parameter 5-15
[0] No
33
Terminal 33
operation
Digital Input
37, 38
–
STO
Analog inputs/outputs
Parameter 6-91
[0] No
42
Terminal 42
operation
Analog Output
50
–
+10 V DC
Parameter
53
group 6-1*
Analog input 53
Parameter
54
group 6-2*
Analog input 54
55
–
Table 4.1 Terminal Descriptions - Digital Inputs/Outputs,
Analog Inputs/Outputs
Default
Description
setting
Selectable for
either digital
input, digital
output, or pulse
output. The
default setting is
digital input.
Digital input.
Digital input, 24 V
encoder. Terminal
33 can be used for
pulse input.
Functional safety
inputs.
Programmable
analog output. The
analog signal is 0–
20 mA or 4–
20 mA at a
maximum of
500 Ω. Can also
be configured as
digital outputs.
10 V DC analog
supply voltage.
15 mA maximum
commonly used
for potentiometer
or thermistor.
Analog input. Only
voltage mode is
–
supported. It can
also be used as
digital input.
Analog input.
Selectable
–
between voltage
or current mode.
Common for
–
digital and analog
inputs.
19
4
4
Need help?
Do you have a question about the VLT Midi Drive FC 280 and is the answer not in the manual?