Table 2: Installer Configuration Menu (Part 3 of 6)
Parameter
Description and Default
Appearing
on Display
Pband
Sets the proportional band used by
the controller Proportional-Integral
(PI) control loop.
Default: 2.0F°/1.1C°
Note: The proportional band
default setting of 2.0F°/1.1C°
provides satisfactory controller
operation in most instances. A
proportional band setting other than
the default is normally used in
installations where the location of
the controller is problematic, leading
to unwanted cycling. An example of
a problematic installation is a
wall-mounted controller installed
between the return and supply air
feeds, that is directly influenced by
the supply air stream.
Anticycl
Anti-Short Cycle timer sets the
minimum on/off times for heating
and cooling.
Default: 2.0 min
Note: Set the anti-short cycle timer
to 0.0 min for equipment that
already has its own anti-short cycle
timer.
Heat cph
Sets the maximum number of
Heating cycles per hour.
Default: 4.0
Cool cph
Sets the maximum number of
Cooling cycles per hour.
Default: 4.0
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 2.0F°/1.0C°
Fan cont
Determines how the fan is activated
in response to a call for heating.
Default: on
Note: The Fan cont parameter
applies to W1 and W2 when the fan
is in the Auto mode only. The Fan
cont parameter does not affect fan
operation on a call for cooling
(Y1 and Y2).
Fan del
Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default off
Note: The fan delay is only active
when the fan is in the Auto mode.
10
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
Installation Instructions
Selection Options
(2): 2.0F°/1.1C°
(3): 3.0F°/1.7C°
(4): 4.0F°/2.2C°
(5): 5.0F°/2.8C°
(6): 6.0F°/3.3C°
(7): 7.0F°/3.9C°
(8): 8.0F°/4.4C°
Range: 0.0 to 5.0 min adjustable in 1-minute increments
Range: 3.0 to 8.0 cycles per hour
Range: 3.0 or 4.0 cycles per hour
Range: 2.0F°/1.0C° to 4.0F°/2.0C° adjustable in 1.0F°/0.5C°
increments
(off): The controller does not activate the fan in response to a call
for heating. The fan is activated by the equipment fan and limit
control.
(on): Enables the controller to activate the fan in response to a call
for heating.
(on): Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off): No extension of fan operation after a heating or cooling cycle
has ended.