Johnson Controls T606MSP-4 Installation Instructions Manual

Johnson Controls T606MSP-4 Installation Instructions Manual

Multi-stage temperature and humidity controllers; t606msx-4 series; t606msx-4+pir series

Advertisement

T606MSx-4 and T606MSx-4+PIR Series Multi-Stage
Temperature and Humidity Controllers

Installation Instructions

T606MSN-4, T606MSP-4,
T606MSN-4+PIR, T606MSP-4+PIR
Applications
The T606MSN-4 and T606MSN-4+PIR
non-programmable and T606MSP-4 and
T606MSP-4+PIR programmable temperature and
humidity controllers are specifically designed for
control of multi-stage commercial heating and cooling
equipment with a humidifier and/or dehumidifier.
IMPORTANT: The T606MSx-4 and
T606MSx-4+PIR Series Temperature and Humidity
Controllers are intended to provide an input to
equipment under normal operating conditions.
Where failure or malfunction of the controller could
lead to personal injury or property damage to the
controlled equipment or other property, additional
precautions must be designed into the control
system. Incorporate and maintain other devices,
such as supervisory or alarm systems or safety or
limit controls, intended to warn of or protect against
failure or malfunction of the controller.
North American Emissions Compliance
United States
This equipment has been tested and found to
comply with the limits for a Class A digital device
pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection
against harmful interference when this equipment is
operated in a commercial environment. This
equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications.
Operation of this equipment in a residential area is
likely to cause harmful interference, in which case
the user will be required to correct the interference
at his/her own expense.
Refer to the
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity
Part No. 24-9890-1354, Rev. A
QuickLIT Web site
for the most up-to-date version of this document.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Installation
Location Considerations
Locate the T606MSx-4 or T606MSx-4+PIR Series
Temperature and Humidity Controller:
on a partitioning wall, approximately 5 ft (1.5 m)
above the floor in a location of average
temperature
away from direct sunlight, radiant heat, outside
walls, outside doors, air discharge grills, or
stairwells; or from behind doors
away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
For integrated Passive Infrared (PIR) models, be sure
that the controller is located centrally, where occupant
movement is abundant.
Note: Allow for vertical air circulation to the controller.
To install the controller:
1. Use a Phillips-head screwdriver to remove the
security screw if it is installed on the bottom of the
controller cover.
Note: Normally, the security screw is packaged
separately in a plastic bag with the controller. Skip
this step if the screw is not installed on the bottom
of the cover.
2. Pull the bottom edge of the controller cover and
open the controller as illustrated in Figure 1.
Controllers Installation Instructions
Issued August 16, 2012
Supersedes December 1, 2010
1

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls T606MSP-4

  • Page 1: Installation Instructions

    Applications Canada The T606MSN-4 and T606MSN-4+PIR This Class (A) digital apparatus meets all the non-programmable and T606MSP-4 and requirements of the Canadian Interference-Causing T606MSP-4+PIR programmable temperature and Equipment Regulations. humidity controllers are specifically designed for control of multi-stage commercial heating and cooling Cet appareil numérique de la Classe (A) respecte...
  • Page 2 Note: PIR models have a wiring connection Note: If you need to install the thermostat on an between the cover and the Printed Circuit Board electrical junction box, use 2-1/2 x 4 in. (63 x 101 (PCB). This connection allows for proper wiring of mm) square boxes with mud ring covers, and avoid the occupancy sensor.
  • Page 3 Wiring Five-Pole When an existing controller is replaced, remove and Left Top Connector Three-Pole label the wires to identify the terminal functions. When Right Top a T606MSx-4 or T606MSx-4+PIR Series Controller is Connector replaced, simply remove the old screw terminal blocks and reinsert them onto the PCB of the replacement controller.
  • Page 4 Independent Contact - Lighting - On/Off Actuation - Exhaust Fan Scom Heat 1 Heat 2 Dehum Output Cool 1 Cool 2 Cool 2 0–10 VDC Outdoor 0–10 VDC 24 VAC Remote High Limit Thermostat Controller Room Temperature Humidity Power Humidity Sensor Sensor Sensor...
  • Page 5: Setup And Adjustments

    Note: %RH disp must be set to ON to display access the Installer Configuration Menu or to humidity. exit the menu (See Configuring the • Day and Time (T606MSP-4 and T606MSP-4+PIR T606MSx-4 or T606MSx-4+PIR Series Models) Controller on page 8.) •...
  • Page 6: Dehumidification Operation

    Humidification Operation High Limit Humidity Sensor Operation Humidification operates only when the controller is in The T606MSx-4(+PIR) Series Temperature and heating mode (system mode = Heat, or system mode = Humidity Controller includes a high limit sequence. Auto and mode at the controller is Heat). If a call for This sequence allows the use of a remote 0 to 10 VDC humidification occurs and the fan is off, the fan is first humidity sensor to keep the humidifier from saturating...
  • Page 7: Occupancy Sensor Operation - T606Msx-4+Pir Series Controllers

    If Dehumidification Lockout (Dhu LCK) is set to Off: The controller automatically switches the occupancy level between Occupied and Unoccupied as required, Dehumidification operates when the controller is in any when local movement is sensed. In the Occupied mode except Off. If a dehumidification demand exists mode, if no movement is detected beyond the Unocc and the fan is off, the fan is first turned on, then the TM parameter setting, the mode changes to...
  • Page 8: Configuring The Digital Input

    Configuring the T606MSx-4 or T606MSx-4+PIR 3. When the desired parameter is displayed, use the YES key to choose the desired selection option. Series Controller The T606MSx-4 and T606MSx-4+PIR Series 4. Press the YES key and then the NO key to Controllers ship from the factory with default settings continue scrolling through the parameters.
  • Page 9 Table 2: Installer Configuration Menu (Part 2 of 6) Parameter Description and Default Selection Options Appearing on Display MenuScro Gives the option of having the (off): The scroll is inactive. display continuously scroll the (on): The scroll is active. parameters. Default: on Lockout Selectable Lockout Levels for...
  • Page 10 Table 2: Installer Configuration Menu (Part 3 of 6) Parameter Description and Default Selection Options Appearing on Display Pband Sets the proportional band used by (2): 2.0F°/1.1C° the controller Proportional-Integral (3): 3.0F°/1.7C° (PI) control loop. (4): 4.0F°/2.2C° Default: 2.0F°/1.1C° (5): 5.0F°/2.8C° Note: The proportional band (6): 6.0F°/3.3C°...
  • Page 11 Table 2: Installer Configuration Menu (Part 4 of 6) Parameter Description and Default Selection Options Appearing on Display TOccTime Sets the duration of the Temporary Range: 0.0 to 12.0 hrs adjustable in 1-hour increments Occupancy Time (when the controller is in the Unoccupied mode) when a Schedule Override Function is enabled using either the Main User Menu or DI1 or DI2...
  • Page 12 Table 2: Installer Configuration Menu (Part 5 of 6) Parameter Description and Default Selection Options Appearing on Display Unocc TM Sets the time delay between the Range: 0.5 hours to 24.0 hours adjustable in 0.5 hour increments moment when the controller toggles from the Occupied mode to the Unoccupied mode after the last motion is detected by the...
  • Page 13: Operation

    0% RH Setting DI to RemNSB disables schedules and stops the Schedule menu display. Any other setting enables schedules and the Schedule menu (T606MSP-4 and T606MSP-4+PIR models). T606MSP-4 and T606MSP-4+PIR models. When adjusting the numeric value, press the UP/DOWN arrow key to change the value by single increments; press and hold the UP/DOWN arrow key to change the numeric value in increments of ten.
  • Page 14: Enabling Temporary Override Schedule

    Note: Schedule Set and Clock Set are available on for the Occupied and Unoccupied modes, follow the the T606MSP-4 and T606MSP-4+PIR models only. steps in Table 4. When changing the temperatures, press and release the keys to change the temperature Enabling Temporary Override Schedule in 0.5F°/0.5C°...
  • Page 15: Entering Temporary Temperature Setpoints

    Table 4: Entering Permanent Temperature Table 4: Entering Permanent Temperature Setpoints (Part 1 of 2) Setpoints (Part 2 of 2) Controller Description Controller Description Display Display Press the MENU key while in the Press the UP/DOWN arrow keys to Status Display Menu to enter the set the temperature.
  • Page 16: Entering Humidity Setpoints

    Entering Humidity Setpoints Selecting the System Mode You can enter setpoints for humidification and The controller has four system modes: dehumidification after configuring the temperature • Automatic Mode (auto): Automatic changeover setpoints. A fixed 5% RH deadband is present between between heating and cooling.
  • Page 17 Table 8. See Table 10, Events 1 heating or cooling in Unoccupied states. This is the and 2, for an example of a two-event office schedule. default setting for the T606MSP-4 and Table 8: Programming the Daily Schedule – T606MSP-4+PIR models.
  • Page 18 Programming the Daily Schedule – Four-Event set the first Occupied start time. Occupied Press the YES key to enter the time. (T606MSP-4 and T606MSP-4+PIR Models) 12:00 AM The schedule-setting menu is used to enter the Occupied and Unoccupied states for each day of the Press the UP/DOWN arrow keys to week.
  • Page 19 Programming different events to the same time for that day cancels those events and leaves the controller in the Unoccupied state. Setting the Day and Time (T606MSP-4 and Table 11: Setting the Day and Time (Part 2 of 2) T606MSP-4+PIR Models)
  • Page 20: Setting Schedule Hold

    Setting the Day and Time Occupied state via the Occupied setpoints. (T606MSP-4 and T606MSP-4+PIR Models) procedure. Occupied hold appears in the Status Display Menu Setting Schedule Hold when this selection is active.
  • Page 21: Repair Information

    Additional TE-636xx-x Series 10k ohm Johnson Controls Type II Thermistor Sensors are available; refer to the TE-6300 Series Temperature Sensors Product Bulletin (LIT-216320) for more details.
  • Page 22: Technical Specifications

    The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.