Smart Fan Mode (smart): Energizes the fan all
the time for Occupied states, and only on a call for
heating or cooling in Unoccupied states. This is the
default setting for the T606MSP-4 and
T606MSP-4+PIR models.
To select the fan mode, follow the steps in Table 7:
Table 7: Selecting the Fan Mode
Controller
Description
Display
Press the MENU key while in the
Status Display Menu to enter the
RoomTemp
Main User Menu.
75.0 ° F
Press the NO key for all prompts
until the fan mode prompt appears
Fan mode
on the display. Press the YES key to
set? Y/N
enter the fan mode setting menu.
Press the UP/DOWN arrow keys to
locate the desired fan mode. Press
Fan mode
the YES key to select the desired
Smart
system mode (example for smart
mode shown)
Press the YES key to return to
the Status Display Menu or press
Exit?
the NO key to return to the
Y/N
system mode selection menu.
Programming the Daily Schedule – Two-Event
(T606MSP-4 and T606MSP-4+PIR Models)
The schedule-setting menu is used to enter the
Occupied or Unoccupied states for each day of the
week. The schedule-setting menu reflects either a
two- or a four-event schedule per day, based on what
was selected in the 2/4event parameter during the
configuration process. If the schedule-setting menu
does not reflect a two-event schedule, select two
events in the 2/4event parameter of the Installer
Configuration Menu.
When changing the time, press and release the
UP/DOWN arrow keys to change the time in 1-minute
increments; press and hold down the keys to change
the time in 30-minute increments.
Note: Programming one of the digital inputs to remote
NSB disables the menu.
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
Installation Instructions
To set the time schedule for a two-event schedule,
follow the steps in Table 8. See Table 10, Events 1
and 2, for an example of a two-event office schedule.
Table 8: Programming the Daily Schedule –
Two-Event (Part 1 of 2)
Controller
Description
Display
Press the MENU key while in the
Status Display Menu to enter the
RoomTemp
Main User Menu.
75.0 ° F
Press the NO key for all prompts until
the schedule set prompt appears on
Schedule
the display. Press the YES key to
set? Y/N
enter the scheduling menu.
Press the YES key to set the
schedule for Monday or press the
Monday
NO key to advance to Tuesday.
set? Y/N
Press the YES key to set the
Occupied start time for Monday or
Occupied
press the NO key to advance to
day? Y/N
Tuesday. Selecting NO leaves the
controller in the Unoccupied state for
the entire day.
Press the UP/DOWN arrow keys to
set the Occupied start time. Press the
Occupied
YES key to enter the time.
12:00 AM
Press the UP/DOWN arrow keys to
set the Unoccupied start time. Press
Unoccup
the YES key to enter the time.
12:00 AM
Press the YES key to set the
schedule for Tuesday or press the
Tuesday
NO key to advance to Wednesday.
set? Y/N
Press the YES key to copy the
schedule from the previous day.
Copy Y/N
Press the NO key to set a different
previous
schedule.
If the YES key was pressed, the next
prompt is for Wednesday. Repeat the
Wednesda
procedure for the rest of the days of
set? Y/N
the week.
17