Johnson Controls T606MSP-4 Installation Instructions Manual page 11

Multi-stage temperature and humidity controllers; t606msx-4 series; t606msx-4+pir series
Table of Contents

Advertisement

Table 2: Installer Configuration Menu (Part 4 of 6)
Parameter
Description and Default
Appearing
on Display
TOccTime
Sets the duration of the Temporary
Occupancy Time (when the
controller is in the Unoccupied
mode) when a Schedule Override
Function is enabled using either the
Main User Menu or DI1 or DI2
configured as a temporary override
remote contact (RemOVR).
Sets the effective duration of the
Temporary heating or cooling
setpoints set using the
UP/DOWN arrow keys.
Default: 3.0 hrs
Cal RS
Sets the desired room air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°C
Cal OS
Sets the desired outside air
temperature sensor calibration
(offset). The offset can be added to
or subtracted from the actual
displayed room temperature.
Default: 0.0F°/0.0C°
H stage
Reverts the operation of a two-stage
controller to a single-stage controller
when the second heating stage is
not needed.
Default: 2.0
C stage
Reverts the operation of a two-stage
controller to a single-stage controller
when the second cooling stage is
not needed.
Default: 2.0
H lock
Disables heating stage(s) operation
when the outside air temperature is
greater than the configured value. If
the fan mode is set to Auto or
Smart, the fan output is also
disabled. Requires that an outside
air temperature sensor be installed
and connected.
Default: 120°F/49°C
C lock
Disables cooling stage(s) operation
when the outside air temperature is
less than the configured value. If the
fan mode is set to Auto or Smart,
the fan output is also disabled.
Requires that an outside air
temperature sensor be installed and
connected.
Default: -40°F/-40°C
T606MSx-4 and T606MSx-4+PIR Series Multi-Stage Temperature and Humidity Controllers
Installation Instructions
Selection Options
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments
Range: -5.0F°/-2.5C° to 5.0F°/2.5C° adjustable in 1.0F°/0.5C°
increments
Range: -5.0F°/-2.5C° to 5.0F°2.5C° adjustable in 1.0F°/0.5C°
increments
(1.0): One Stage
(2.0): Two Stages
(1.0): One Stage
(2.0): Two Stages
Range: -15°F/-26°C to 120°F/49°C adjustable in 5F°/5C° increments
Range: -40°F/-40°C to 95°F/35°C adjustable in 5F°/5C° increments
11