Quick Links

TE-6300M Series Well Insertion Temperature Sensors

Installation Instructions

TE-631xM, TE-635xM,
TE-634xM, TE-636xM
Applications
IMPORTANT: The TE-6300M Series Well Insertion
Temperature Sensors are intended to provide an
input to equipment under normal operating
conditions. Where failure or malfunction of the
sensor could lead to personal injury or property
damage to the controlled equipment or other
property, additional precautions must be designed
into the control system. Incorporate and maintain
other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or
protect against failure or malfunction of the sensor.
IMPORTANT : Le TE-6300M Series Well Insertion
Temperature Sensor est destiné à transmettre des
données entrantes à un équipement dans des
conditions normales de fonctionnement. Lorsqu'une
défaillance ou un dysfonctionnement du sensor
risque de provoquer des blessures ou
d'endommager l'équipement contrôlé ou un autre
équipement, la conception du système de contrôle
doit intégrer des dispositifs de protection
supplémentaires. Veiller dans ce cas à intégrer de
façon permanente d'autres dispositifs, tels que des
systèmes de supervision ou d'alarme, ou des
dispositifs de sécurité ou de limitation, ayant une
fonction d'avertissement ou de protection en cas de
défaillance ou de dysfonctionnement du sensor.
Installation
IMPORTANT: Do not install the TE-6300M Series
Well Insertion Temperature Sensor in ambient
temperatures beyond the specified -50 to 220°F
(-46 to 104°C) temperature range. Installing the
temperature sensor in ambient temperatures
beyond this range may damage the unit and void the
warranty.
Refer to the
TE-6300M Series Well Insertion Temperature Sensors Installation Instructions
2 4 - 4 0 3 4 - 1 8 2 ,
Part No. 24-4034-182, Rev. G
QuickLIT website
for the most up-to-date version of this document.
Dimensions
4.73 (120.1) maximum
7.73 (196.3) maximum
Side View
1.87 (47.5)
0.60 (15.2)
1.87
(47.5)
(30.5)
Front View
Figure 1: Sensor Dimensions, in. (mm)
Mounting
Location Considerations
Consider the following mounting location guidelines:
Avoid areas subject to the effects of excessive
vibration, electrical noise, direct sunlight, or radiant
heat.
Keep electrical wiring as short as possible to
minimize temperature error.
Mounting the Temperature Sensor
See Figure 2 and mount the temperature sensor:
Sensor
Probe
Figure 2: Installing the Well Insertion Sensor
Re v .
G
Issued March 2016
1.80 (45.7)
0.875
(22.2)
1.20
Direct Mount for
6 in. (152 mm) Probe Models
Set Screw
TE-6300W-101
TE-6300W-102
Thermowell
or
Threaded Mount for
8 in. (203 mm) Probe Models
1/2 in.
NPT
Well Adaptor
Set Screw
TE-6300W-110 Thermowell
1

Advertisement

loading

Summary of Contents for Johnson Controls TE-631xM

  • Page 1: Installation Instructions

    2 4 - 4 0 3 4 - 1 8 2 , Re v . TE-6300M Series Well Insertion Temperature Sensors Installation Instructions Part No. 24-4034-182, Rev. G TE-631xM, TE-635xM, Issued March 2016 TE-634xM, TE-636xM Refer to the QuickLIT website for the most up-to-date version of this document.
  • Page 2 Sensor’s electrical ratings. Repair Information f the TE-6300M Series Well Insertion Temperature Sensor fails to operate within its specifications, replace the unit. For a replacement sensor, contact the nearest Johnson Controls representative. TE-6300M Series Well Insertion Temperature Sensors Installation Instructions...
  • Page 3 The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

This manual is also suitable for: