4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
4 - 16
(3) Operating procedure
Perform settings, starting with the GX Developer I/O assignment screen.
(a) I/O assignment screen
Specify the following for the slot where the
QD62(E/D) is mounted.
Type
: Select "Intelli."
Model name : Enter the module's model name.
Points
: Select 16 points.
Start XY
: Enter the start I/O signal for the
QD62(E/D).
(b) Switch setting for I/O and intelligent function
module
Click on Switch Setting on the I/O assignment
screen to display the screen at left and set
switches 1 to 5. The setting can easily be done if
values are entered in hexadecimal. Change the
input format to hexadecimal and enter values.
(c) Intelligent function module detailed setting
Click on Detailed Setting on the I/O
assignment screen to display the screen at left,
and then set the error time output mode and H/W
error time PLC operation mode.
MELSEC-Q
4 - 16