Mitsubishi Electric QD62 User Manual page 79

Melsec system q, programmable logic controller, high-speed counter module, gx configurator-ct
Hide thumbs Also See for QD62:
Table of Contents

Advertisement

7 UTILITY PACKAGE (GX Configurator-CT)
7 - 14
[Explanation of items]
(1) Contents of the screen display
Module side buffer
size
Module side transfer
word count
Transfer direction
PLC side device
(2) Explanation of the command buttons
Make text file
End setup
Cancel
POINTS
• The auto refresh settings are stored in the intelligent module parameters. Once
the intelligent module parameters are written to the CPU module, they can be
enabled by turning the power OFF and then ON, or resetting the CPU module.
• Auto refresh settings cannot be changed from the sequence program. However,
it is possible to add a process similar to auto refresh by using the FROM/TO
commands of the sequence program.
: Displays the size of the setting item buffer memory.
: Displays the number of words to transfer.
: " " indicates that data at the PLC CPU side is written to
the buffer memory.
" " indicates that data is read from the buffer memory to
the PLC CPU side.
: Enter the device at the CPU module to be automatically
refreshed.
The devices that can be used include X, Y, M, L, B, T, C,
ST, D, W, R, and ZR. When using bit devices, X, Y, M, L
or B, set a number that can be divided by 16 points
(examples: X10, Y120, M16).
Also, buffer memory data is stored in 16-point portions
starting with the device number that has been set. For
example, if X10 is set, data will be stored to X10 through
X1F.
Creates a file containing the displayed screen data in a text
file format.
Confirms the entry of set data and ends the operation.
Cancels the set data and ends the operation.
MELSEC-Q
7 - 14

Advertisement

Table of Contents
loading

This manual is also suitable for:

Qd62eQd62dSw0d5c-qctu-e