3 SPECIFICATIONS

3.5 Interface with External Devices

I/O
Internal circuit
classification
Input
Output
To the fuse
broken detection
circuit
1: Terminal numbers A03, A04, B03 and B04 are not used.
3 - 11
The table below lists the external device interface for the QD62(E/D).
(1) QD62 (DC input sinking output type)
Terminal
number
1
CH1
CH2
4.7k
1/3W
A20
A13
3.3k
1/10W
B20
B13
470
1/16W
A19
A12
B19
B12
4.7k
1/3W
A18
A11
3.3k
1/10W
B18
B11
470
1/16W
A17
A10
10k
1/3W
B17
B10
5.6k
1/10W
A16
A09
2k
1k
1/10W
1/10W
B16
B09
A15
B08
10k
1/3W
B15
B08
5.6k
1/10W
A14
A07
2k
1k
1/10W
1/10W
B14
B07
A06
A05
B06
B05
B02, B01
FUSE
A02, A01
Signal name
Phase A pulse input 24 V
Phase A pulse input 12 V
Phase A pulse input 5 V
ABCOM
Phase B pulse input 24 V
Phase B pulse input 12 V
Phase B pulse input 5 V
Preset input 24 V
Preset input 12 V
Preset input 5 V
CTRLCOM
Function start input 24 V
Function start input 12 V
Function start input 5 V
EQU1
(Coincidence output point No. 1)
EQU2
(Coincidence output point No. 2)
12/24 V
0 V
Input voltage
Operation
(guaranteed value)
When ON
21.6 to 26.4 V
When OFF
5 V or less
When ON
10.8 to 13.2 V
When OFF
4 V or less
When ON
4.5 to 5.5 V
When OFF
2 V or less
When ON
21.6 to 26.4 V
When OFF
5 V or less
When ON
10.8 to 13.2 V
When OFF
4 V or less
When ON
4.5 to 5.5 V
When OFF
2 V or less
When ON
21.6 to 26.4 V
When OFF
5 V or less
When ON
10.8 to 13.2 V
When OFF
4 V or less
When ON
4.5 to 5.5 V
When OFF
2 V or less
Response
OFF
ON
time
0.5 ms or less
When ON
21.6 to 26.4 V
When OFF
5 V or less
When ON
10.8 to 13.2 V
When OFF
4 V or less
When ON
4.5 to 5.5 V
When OFF
2 V or less
Response
OFF
ON
time
0.5 ms or less
Operating voltage
10.2 to 30 V
Maximum load current
0.5 A/point, 2 A/1 common
Maximum voltage drop when ON 1.5 V
Response time OFF
ON 0.1 ms or less
ON
OFF 0.1 ms or less (rated load,
resistive load)
Input voltage
10.2 to 30 V
Current consumption
8 mA (TYP 24 V DC)
MELSEC-Q
Operating current
(guaranteed value)
2 to 5 mA
0.1 mA or less
2 to 5 mA
0.1 mA or less
2 to 5 mA
0.1 mA or less
2 to 5 mA
0.1 mA or less
2 to 5 mA
0.1 mA or less
2 to 5 mA
0.1 mA or less
2 to 5 mA
0.1 mA or less
2 to 5 mA
0.1 mA or less
2 to 5 mA
0.1 mA or less
ON
OFF
1 ms or less
2 to 5 mA
0.1 mA or less
2 to 5 mA
0.1 mA or less
2 to 5 mA
0.1 mA or less
ON
OFF
1 ms or less
3 - 11