Siemens SINAMICS G110 Operating Instructions Manual page 51

120 w - 3 kw
Hide thumbs Also See for SINAMICS G110:
Table of Contents

Advertisement

04/2005
3.4.8 Cloning Parameters with the BOP
Warning
During the download of parameters from the BOP to the inverter, the digital output
may produce a spurious signal. Prior to performing a download from the BOP to
the inverter appropriate counter-measures must be taken to ensure that any
suspended load is secured, for example, by the use of external brakes or the load
being lowered to ground level and secured.
A single parameter set can be uploaded from an inverter and then downloaded into
another inverter. To clone a parameter set from one inverter to another, the
following procedure should be performed:
1. Connect the Basic Operator Panel (BOP) to the inverter.
2. Ensure that it is safe to stop the inverter.
3. Stop the inverter.
4. Set parameter P0003 to 3.
5. Set parameter P0010 to 30 to enter Cloning Mode.
6. Set parameter P0802 to 1 to start the upload from the Inverter to the BOP.
7. During the upload "BUSY" will be displayed.
8. The BOP and the inverter will not react to any commands during upload.
9. If the upload has been completed successfully, the BOP display will return
to normal and the inverter will return to a ready state.
10. If the upload has failed:
11. The BOP can now be removed from the inverter.
12. Connect the BOP to the new inverter.
13. Ensure power is applied to the inverter.
14. Set parameter P0003 to 3.
15. Set parameter P0010 to 30 to enter Cloning Mode.
16. Set parameter P0803 to 1 to start the download from the BOP to the
inverter.
17. During the download "BUSY" will be displayed.
18. During download the BOP and the inverter will not react to any commands
during download.
19. If the download has been completed successfully, the BOP display will
return to normal and the inverter will return to a ready state.
20. If the download has failed:
21. The BOP can now be removed from the inverter.
The following important restrictions should be considered when using the Cloning
procedure:
Only the current dataset is uploaded to the BOP.
SINAMICS G110
Operating Instructions
6SL3298-0AA11-0BP0
a. Attempt another upload.
or
b. Perform a factory reset.
a. Attempt another download.
or
b. Perform a factory reset.
Commissioning
51

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents