04/2005
Table 7-5
Frame Sizes B and C;
input voltage 1 AC 200 V – 240 V, ± 10 %, power range 1.1 kW - 3.0 kW
Frame Size
Motor Output Rating
Order No.
analog
Unfiltered
USS
analog
Filtered
USS
2
Output Current
3
Input Current
Recommended Fuse
Input Cable
Output Cable
1
The horsepower (hp) ratings are obtained by comparison to the Siemens 1LA6 and 1LA7 motors and
not NEMA/UL rated motors.
2
Current data applies for an ambient temperature of 50ºC unless otherwise specified
3
The value applies to the rated mains voltage of 230 V
* Indicates the last digit of the Order No. may change due to modifications of hardware or software in
the product.
Table 7-6
Power losses SINAMICS G110
(230 V) inverters
Frame size
Output Power
(kW)
A
0.12
A
0.25
A
0.37
A
0.55
A
0.75
B
1.1
B
1.5
C
2.2
C
*The losses given in Table 7-6 are applicable for units fitted with 25 m of screened cable
SINAMICS G110
Operating Instructions
6SL3298-0AA11-0BP0
B
[kW]
1.1
1
[hp]
1.5
0AB21-1UA0*
0AB21-1UB0*
0AB21-1AA0*
0AB21-1AB0*
[A]
6.0
[A]
14.7
[A]
20.0
3NA3807
2
[mm
]
2.5 – 6.0
[AWG]
12 – 10
2
[mm
]
1.5 – 6.0
[AWG]
14 – 10
Losses (W)
22
28
36
43
54
86
118
174
3
210
SINAMICS G110 Specifications
B
C
1.5
2.2
2.0
3.0
6SL3211-
0AB21-5UA0*
0AB22-2UA0*
0AB21-5UB0*
0AB22-2UB0*
0AB21-5AA0*
0AB22-2AA0*
0AB21-5AB0*
0AB22-2AB0*
7.8 (40ºC)
11.0
19.7
27.2
25.0
35.0
3NA3810
3NA3814
2.5 – 6.0
4.0 – 10
12 – 10
11 – 8
1.5 – 6.0
2.5 – 10
14 – 10
12 – 8
C
3.0
4.0
0AB23-0UA0*
0AB23-0UB0*
0AB23-0AA0*
0AB23-0AB0*
13.6 (40ºC)
32.0
50.0
3NA3820
6.0 – 10
10 – 8
2.5 – 10
12 – 8
69