GE L60 Instruction Manual page 597

Line phase comparison system ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 29 of 59)
ADDR
REGISTER NAME
707E
Phase Distance Zone 1 Quad Right Blinder
707F
Phase Distance Zone 1 Quad Right Blinder RCA
7080
Phase Distance Zone 1 Quad Left Blinder
7081
Phase Distance Zone 1 Quad Left Blinder RCA
7082
Phase Distance Zone 1 Volt Limit
7083
Phase Distance Zone 1 Transformer Voltage Connection
7084
Phase Distance Zone 1 Transformer Current Connection
7085
Phase Distance Zone 1 Rev Reach
7086
Phase Distance Zone 1 Rev Reach RCA
7087
Reserved (10 items)
7091
...Repeated for Phase Distance Zone 2
70B2
...Repeated for Phase Distance Zone 3
Ground Distance (Read/Write Grouped Setting) (3 modules)
7130
Ground Distance Zone 1 Function
7131
Ground Distance Zone 1 Current Supervision
7132
Ground Distance Zone 1 Reach
7133
Ground Distance Zone 1 Direction
7134
Ground Distance Zone 1 Comparator Limit
7135
Ground Distance Zone 1 Delay
7136
Ground Distance Zone 1 Block
7138
Ground Distance Zone 1 Target
7139
Ground Distance Zone 1 Events
713A
Ground Distance Zone 1 Shape
713B
Ground Distance Zone 1 Z0 Z1 Magnitude
713C
Ground Distance Zone 1 Z0 Z1 Angle
713D
Ground Distance Zone 1 RCA
713E
Ground Distance Zone 1 DIR RCA
713F
Ground Distance Zone 1 DIR Comp Limit
7140
Ground Distance Zone 1 Quad Right Blinder
7141
Ground Distance Zone 1 Quad Right Blinder RCA
7142
Ground Distance Zone 1 Quad Left Blinder
7143
Ground Distance Zone 1 Quad Left Blinder RCA
7144
Ground Distance Zone 1 Z0M Z1 Magnitude
7145
Ground Distance Zone 1 Z0M Z1 Angle
7146
Ground Distance Zone 1 Voltage Level
7147
Ground Distance Zone 1 Non-Homogeneous Angle
7148
Ground Distance Zone 1 POL Current
7149
Ground Distance Zone 1 Reverse Reach
717A
Ground Distance Zone 1 Reverse Reach RCA
714B
Reserved (7 items)
7152
...Repeated for Ground Distance Zone 2
7174
...Repeated for Ground Distance Zone 3
Line Pickup (Read/Write Grouped Setting)
71E0
Line Pickup Function
71E1
Line Pickup Signal Source
71E2
Line Pickup Phase IOC Pickup
71E3
Line Pickup UV Pickup
71E4
Line End Open Pickup Delay
71E5
Line End Open Reset Delay
71E6
Line Pickup OV Pickup Delay
71E7
Autoreclose Coordination Pickup Delay
71E8
Autoreclose Coordination Reset Delay
71E9
Autoreclose Coordination Bypass
71EA
Line Pickup Block
GE Multilin
RANGE
0.02 to 500
60 to 90
0.02 to 500
60 to 90
0 to 5
0 to 12
0 to 12
0.02 to 500
30 to 90
---
0 to 1
0.05 to 30
0.02 to 500
0 to 2
30 to 90
0 to 65.535
0 to 4294967295
0 to 2
0 to 1
0 to 1
0 to 10
-90 to 90
30 to 90
30 to 90
30 to 90
0.02 to 500
60 to 90
0.02 to 500
60 to 90
0 to 7
-90 to 90
0 to 5
-40 to 40
0 to 1
0.02 to 500
30 to 90
0 to 65535
0 to 1
0 to 5
0 to 30
0 to 3
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 1
0 to 4294967295
L60 Line Phase Comparison System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
pu
0.001
F001
---
1
F153
---
1
F153
ohms
0.01
F001
degrees
1
F001
---
---
F001
---
1
F102
pu
0.001
F001
ohms
0.01
F001
---
1
F154
degrees
1
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F120
---
0.01
F001
degrees
1
F002
degrees
1
F001
degrees
1
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
---
0.01
F001
degrees
1
F002
pu
0.001
F001
degrees
0.1
F002
---
1
F521
ohms
0.01
F001
degrees
1
F001
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
pu
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F102
---
1
F300
DEFAULT
1000
85
1000
85
0
B
0 (None)
0 (None)
200
85
0
0 (Disabled)
200
200
0 (Forward)
90
0
0
0 (Self-reset)
0 (Disabled)
0 (Mho)
270
0
85
85
90
1000
85
1000
85
0
0
0
0
0 (Zero-seq)
200
85
0
0 (Disabled)
0 (SRC 1)
1000
700
150
90
40
45
5
1 (Enabled)
0
B-37