5.6 CONTROL ELEMENTS
The following settings are available.
TRIP BUS 1 BLOCK: The trip bus output is blocked when the operand assigned to this setting is asserted.
TRIP BUS 1 PICKUP DELAY: This setting specifies a time delay to produce an output depending on how output is
used.
5
TRIP BUS 1 RESET DELAY: This setting specifies a time delay to reset an output command. The time delay should be
set long enough to allow the breaker or contactor to perform a required action.
TRIP BUS 1 INPUT 1 to TRIP BUS 1 INPUT 16: These settings select a FlexLogic operand to be assigned as an input
to the trip bus.
TRIP BUS 1 LATCHING: This setting enables or disables latching of the trip bus output. This is typically used when
lockout is required or user acknowledgement of the relay response is required.
TRIP BUS 1 RESET: The trip bus output is reset when the operand assigned to this setting is asserted. Note that the
operand is pre-wired to the reset gate of the latch, As such, a reset command the front panel interface or via
RESET OP
communications will reset the trip bus output.
SETTINGS
TRIP BUS 1 INPUT 1
TRIP BUS 1 INPUT 2
TRIP BUS 1 INPUT 16
SETTINGS
TRIP BUS 1
FUNCTION
TRIP BUS 1 BLOCK
SETTINGS
TRIP BUS 1
LATCHING
TRIP BUS 1 RESET
FLEXLOGIC OPERAND
RESET OP
5-234
Figure 5–120: TRIP BUS FIELDS IN THE PROTECTION SUMMARY
= Off
= Off
OR
AND
= Off
= Enabled
AND
= Off
= Enabled
= Off
OR
Figure 5–121: TRIP BUS LOGIC
L60 Line Phase Comparison System
SETTINGS
TRIP BUS 1 PICKUP
DELAY
Non-volatile,
TRIP BUS 1 RESET
set-dominant
DELAY
S
T
PKP
Latch
T
RST
R
5 SETTINGS
FLEXLOGIC OPERAND
TRIP BUS 1 OP
FLEXLOGIC OPERAND
TRIP BUS 1 PKP
842023A1.CDR
GE Multilin