User-Programmable Pushbuttons - GE L60 Instruction Manual

Line phase comparison system ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

5 SETTINGS
SETTING
CONTROL PUSHBUTTON
{
1 FUNCTION:
Enabled=1
SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL
Enabled=1
SYSTEM SETUP/
BREAKERS/BREAKER 2/
BREAKER 2 PUSHBUTTON
CONTROL
Enabled=1
PATH: SETTINGS
PRODUCT SETUP
 USER PUSHBUTTON 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
:
AND
RUN
OFF
ON
:
Figure 5–12: CONTROL PUSHBUTTON LOGIC


USER-PROGRAMMABLE PUSHBUTTONS

PUSHBUTTON 1
FUNCTION: Disabled
PUSHBTN 1 ID TEXT:
PUSHBTN 1 ON TEXT:
PUSHBTN 1 OFF TEXT:
PUSHBTN 1 HOLD:
0.0 s
PUSHBTN 1 SET:
Off
PUSHBTN 1 RESET:
Off
PUSHBTN 1 AUTORST:
Disabled
PUSHBTN 1 AUTORST
DELAY: 1.0 s
PUSHBTN 1 REMOTE:
Off
PUSHBTN 1 LOCAL:
Off
PUSHBTN 1 DROP-OUT
TIME: 0.00 s
PUSHBTN 1 LED CTL:
Off
PUSHBTN 1 MESSAGE:
Disabled
PUSHBUTTON 1
EVENTS: Disabled
L60 Line Phase Comparison System
5.2 PRODUCT SETUP
TIMER
FLEXLOGIC OPERAND
0
CONTROL PUSHBTN 1 ON
100 msec
842010A2.CDR
5.2.13 USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1(16)
Range: Self-Reset, Latched, Disabled
Range: Up to 20 alphanumeric characters
Range: Up to 20 alphanumeric characters
Range: Up to 20 alphanumeric characters
Range: 0.0 to 10.0 s in steps of 0.1
Range: FlexLogic operand
Range: FlexLogic operand
Range: Disabled, Enabled
Range: 0.2 to 600.0 s in steps of 0.1
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 60.00 s in steps of 0.05
Range: FlexLogic operand
Range: Disabled, Normal, High Priority
Range: Disabled, Enabled
5
5-73