Multi-Terminal Lines; Charging Current Compensation - GE L60 Instruction Manual

Line phase comparison system ur series
Hide thumbs Also See for L60:
Table of Contents

Advertisement

8 THEORY OF OPERATION
8.1 OVERVIEW

8.1.8 MULTI-TERMINAL LINES

Up to this point these discussions have pertained principally to two-terminal lines. Phase comparison schemes are often
applied to lines having more than two terminals and those applications differ somewhat depending on the channel equip-
ment.
a) ON-OFF CHANNEL
The ON-OFF channel equipment is invariably used in blocking type carrier schemes similar to that of Figure 8-16. Since
this type of scheme utilizes only one common frequency for all the transmitters and receivers, Figure 8-16 will apply to
multi-terminal lines as well as two terminal lines. A blocking signal sent from any terminal will be received at all the other
terminals to provide the necessary blocking via the single receiver at that terminal.
b) FREQUENCY SHIFT CHANNEL
Frequency-shift channels are generally used in tripping type schemes. Figure 8-17 illustrates a three-terminal line tripping
scheme using a frequency-shift channel. This arrangement requires two receivers at each terminal. One receiver is
required for each remote transmitter because each transmitter is operated at a different frequency. In order to trip, a high-
shift output is required from both receivers concurrently to AND5. A two-terminal line scheme would require only one
receiver which would operate directly into AND1 without the need for AND5. Each channel has its own symmetry adjust-
ment.
8
Figure 8–18: TRIPPING SCHEME FOR 3-TERMINAL LINE

8.1.9 CHARGING CURRENT COMPENSATION

The basic premise for the operation of phase comparison protection schemes in general, and of the L60 phase comparison
element in particular, is that the sum of the currents entering the protected zone is zero. In the case of a power system
transmission line, this is not entirely true because of the capacitive charging current of the line. For short transmission lines
the charging current is a small factor and can therefore be treated as an unknown error. In this application the L60 can be
deployed without voltage sensors and the line charging current is included as a constant term in the total variance, increas-
ing the differential restraint current. For long transmission lines the charging current is a significant factor, and should be
computed to provide increased sensitivity to fault current.
GE Multilin
L60 Line Phase Comparison System
8-23

Advertisement

Table of Contents
loading

Table of Contents