5 SETTINGS
a) PERMISSIVE OVERREACHING TRANSFER TRIP (POTT)

PATH: SETTINGS
CONTROL ELEMENTS
 POTT SCHEME
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
This scheme is intended for two-terminal line applications only. It uses an over-reaching zone 2 distance element to essen-
tially compare the direction to a fault at both the ends of the line. Ground directional overcurrent functions available in the
relay can be used in conjunction with the zone 2 distance element to key the scheme and initiate its operation. This pro-
vides increased coverage for high resistance faults.
For proper scheme operation, the zone 2 phase and ground distance elements must be enabled, configured, and set per
the rules of distance relaying. The line pickup element should be enabled, configured and set properly to detect line-end-
open/weak-infeed conditions. If used by this scheme, the selected ground directional overcurrent functions must be
enabled, configured, and set accordingly.
POTT PERMISSIVE ECHO: If set to "Enabled" this setting will result in sending a permissive echo signal to the remote
end. The permissive signal is echoed back upon receiving a reliable
line-end-open condition is identified by the line pickup logic. The permissive echo is programmed as a one-shot logic.
The echo is sent only once and then the echo logic locks out for a settable period of time (
duration of the echo pulse does not depend on the duration or shape of the received
.
ECHO DURATION
POTT RX PICKUP DELAY: This setting enables the relay to cope with spurious receive signals. The delay should be
set longer than the longest spurious
delay will increase the response time of the scheme.
GE Multilin



PILOT SCHEMES

POTT SCHEME
POTT SCHEME
FUNCTION: Disabled
POTT PERMISSIVE
ECHO: Disabled
POTT RX PICKUP
DELAY: 0.000 s
TRANS BLOCK PICKUP
DELAY: 0.020 s
TRANS BLOCK RESET
DELAY: 0.090 s
ECHO DURATION:
0.100 s
ECHO LOCKOUT:
0.250 s
LINE END OPEN PICKUP
DELAY:
0.050 s
POTT SEAL-IN
DELAY:
0.400 s
GND DIR O/C FWD:
Off
POTT RX:
Off
POTT SCHEME TARGET:
Self-Reset
POTT SCHEME EVENTS:
Disabled
signal that can occur simultaneously with the zone 2 pickup. The selected
TX
L60 Line Phase Comparison System
5.6 CONTROL ELEMENTS
5.6.10 PILOT SCHEMES
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Self-Reset, Latched, Disabled
Range: Disabled, Enabled
signal from the remote end while the
POTT RX
ECHO LOCKOUT
signal but is settable as
POTT RX
5
setting). The
5-277