C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE
2.
Configure the GOOSE service settings by making the following changes in the

IEC 61850 PROTOCOL
settings menu:
RABLE GOOSE 1
Set
CONFIG GSE 1 FUNCTION
Set
CONFIG GSE 1 ID
Set
CONFIG GSE 1 DST MAC
Set the
CONFIG GSE 1 VLAN PRIORITY
Set the
CONFIG GSE 1 VLAN ID
Set the
CONFIG GSE 1 ETYPE APPID
configuration on the receiver (the default value is "0").
C
Set the
CONFIG GSE 1 CONFREV
this example it can be left at its default value.
3.
Configure the data by making the following changes in the
COL
GGIO1 STATUS CONFIGURATION
Set
GGIO1 INDICATION 1
contact input, virtual input, a protection element status, etc.).
The L60 must be rebooted (control power removed and re-applied) before these settings take effect.
The following procedure illustrates the reception configuration.
1.
Configure the reception dataset by making the following changes in the
61850 PROTOCOL

1
CONFIG GSE 1 DATASET ITEMS
Set
to "GGIO3.ST.Ind1.q" to indicate quality flags for GGIO3 status indication 1.
ITEM 1
Set
to "GGIO3.ST.Ind1.stVal" to indicate the status value for GGIO3 status indication 1.
ITEM 2
The reception dataset now contains a set of quality flags, a single point status Boolean value, and a floating point ana-
log value. This matches the transmission dataset configuration above.
2.
Configure the GOOSE service settings by making the following changes in the

REMOTE DEVICE 1
Set
REMOTE DEVICE 1 ID
Set
REMOTE DEVICE 1 ETYPE APPID
the example above.
Set the
REMOTE DEVICE 1 DATASET
configurable GOOSE 1 in this example, program this value as "GOOSEIn 1".
3.
Configure the data by making the following changes in the
settings menu:
Set
REMOTE IN 1 DEVICE
Set
REMOTE IN 1 ITEM
item to remote input 1.
Remote input 1 can now be used in FlexLogic equations or other settings. The L60 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
C-10
GSSE/GOOSE CONFIGURATION
to "Enabled".
to an appropriate descriptive string (the default value is "GOOSEOut_1").
to a multicast address (for example, 01 00 00 12 34 56).
; the default value of "4" is OK for this example.
value; the default value is "0", but some switches may require this value to be "1".
value. This setting represents the Ethertype application ID and must match the
value. This value changes automatically as described in IEC 61850 part 7-2. For
settings menu:
to a FlexLogic operand used to provide the status of GGIO1.ST.Ind1.stVal (for example, a
GSSE/GOOSE CONFIGURATION
settings menu:
settings menu:
to match the GOOSE ID string for the transmitting device. Enter "GOOSEOut_1".
to match the Ethertype application ID from the transmitting device. This is "0" in
value. This value represents the dataset number in use. Since we are using
to "GOOSEOut_1".
to "Dataset Item 2". This assigns the value of the GGIO3.ST.Ind1.stVal single point status
L60 Line Phase Comparison System

TRANSMISSION

PRODUCT SETUP
PRODUCT SETUP


RECEPTION
CONFIGURABLE GOOSE

INPUTS/OUTPUTS
APPENDIX C

PRODUCT SETUP
COMMUNICATION
CONFIGURABLE GOOSE
CONFIGU-

COMMUNICATION
IEC 61850 PROTO-

COMMUNICATION
CONFIGURABLE GOOSE

INPUTS/OUTPUTS
REMOTE DEVICES

REMOTE INPUTS
REMOTE INPUT 1