Relay Output Connection; Solid-State Switch - Siemens Pointek CLS200 Operating Instructions Manual

Sitrans. capacitance switches
Hide thumbs Also See for Pointek CLS200:
Table of Contents

Advertisement

relay contact:
8 A @ 250 V AC, 2000 VA
5 A @ 30 V DC, 150 W
Switch and potentiometer settings are for illustration purposes only.
Note:

Relay Output Connection

3
2
1
K2
NC
NO
COM

Solid-state Switch

K3
1
2
7ML19985JH01
Pointek CLS200/300 Standard – INSTRUCTION MANUAL
black white
red
switch bank
sensor
delay
sensor
status
output
status
The relay is shown in a de-energized/unpowered state.
K2 contact ratings:
max. switching voltage/current (DC): 30 V DC / 5 A
max. switching voltage/current (AC): 250 V AC / 8 A
max. switching capacity: 150 W / 2000 VA
Solid-state switch to customer's control or instrumentation device.
The switch is shown in de-energized/unpowered state.
K3 contact ratings:
Maximum Voltage: 30 V DC or peak AC
Maximum Current: 82 mA
Non-polarized
trip
point
power on
power supply
12 to 250 V AC/DC
solid state switch:
30 V DC/30 V AC (peak),
82 mA max.