4 PROCEDURE UP TO DATA LINK
4.5.4 Mounting terminating resistors
4 - 17
Use the CL9-TERM (Gray) for the terminating resistor.
For the system configuration using the dedicated flat cables only, the CL9-RYVK
(Black) can be also used. Note that the same type must be used for both ends of the
trunk line.
(1) Mounting terminating resistor to AJ65SBT-CLB side
Mount the terminating resistor to the AJ65SBT-CLB side as shown below.
Note that it should be placed within 20 cm from the AJ65SBT-CLB.
Terminating resistor
(2) Mounting terminating resistor to another end of trunk line
Mount the terminating resistor to the opposite end to the AJ65SBT-CLB side as
shown below.
Within 20cm
AJ65SBT-CLB
Terminating resistor
MELSEC-A