ABB REM 610 Technical Reference Manual page 87

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

1MRS 752263-MUM
Motor protection Relay
Technical Reference Manual
Table 4.1.15-7 Control parameters
Description
Sensor/thermistor selection for input
RTD1
Sensor selection for input RTD2
Sensor selection for input RTD3
Sensor/thermistor selection for input
RTD4
Sensor selection for input RTD5
Sensor selection for input RTD6
Remote control of settings
Entering the SPA password for
settings
Parameter
R, W, P Value
R, W (P) 0 = not in use
1)
V121
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
8 = PTC 0...20 kΩ
R, W (P) 0 = not in use
1)
V122
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
1)
R, W (P) 0 = not in use
V123
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
R, W (P) 0 = not in use
1)
V124
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
8 = PTC 0...20 kΩ
R, W (P) 0 = not in use
1)
V125
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
R, W (P) 0 = not in use
1)
V126
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
V150
R, W
0 = setting group 1
1 = setting group 2
V160
W
1...999
REM 610
87

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents