ABB REM 610 Technical Reference Manual page 139

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

1MRS 752263-MUM
Motor protection Relay
Technical Reference Manual
Table 10.-3Control parameters
Description
Sensor selection for input
RTD3
Sensor/thermistor
selection for input RTD4
Sensor selection for input
RTD5
Sensor selection for input
RTD6
Remote control of settings
Unit address of the relay
Data transfer rate (SPA),
kbps
Rear communication
protocol
Connection type
Line-idle state
Optional communication
module
Parameter
Setting range
(channel 0)
V123
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
V124
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
8 = PTC 0...20 kΩ
V125
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
V126
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
V150
0 = setting group 1
1 = setting group 2
V200
1...254
V201
9.6/4.8
V203
0 = SPA
1 = IEC_103
2 = Modbus RTU
3 = Modbus ASCII
V204
0 = loop
1 = star
V205
0 = light off
1 = light on
V206
0 = not in use
1 = in use
REM 610
Default
Customer's
setting
setting
0
0
0
0
0
1
9.6
0
0
0
0
139

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents