ABB REM 610 Technical Reference Manual page 40

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

REM 610
40
Motor Protection Relay
Technical Reference Manual
Table 4.1.4.12-1 Setting values
Setting
Description
Σt
Restart inhibit value
si
∆Σt
/∆t
Countdown rate of start-up time
s
counter
CBFP
Operate time of CBFP
Ta1>
Alarm value Ta1>
ta1>
Operate time ta1>
Tp1>
Trip value Tp1>
tp1>
Operate time tp1>
Ta2>
Alarm value Ta2>
ta2>
Operate time ta2>
Tp2>
Trip value Tp2>
tp2>
Operate time tp2>
Ta3>
Alarm value Ta3>
ta3>
Operate time ta3>
Tp3>
Trip value Tp3>
tp3>
Operate time tp3>
Ta4>
Alarm value Ta4>
ta4>
Operate time ta4>
Tp4>
Trip value Tp4>
tp4>
Operate time tp4>
Ta5>
Alarm value Ta5>
ta5>
Operate time ta5>
Tp5>
Trip value Tp5>
tp5>
Operate time tp5>
Ta6>
Alarm value Ta6>
ta6>
Operate time ta6>
Tp6>
Trip value Tp6>
tp6>
Operate time tp6>
Thp1>
Trip value Thp1>
Thp2>
Trip value Thp2>
1)
The protected unit scaling factor has only one setting and thus switching between setting groups does
not apply.
2)
The setting step is 0.5.
1MRS 752263-MUM
Setting range
Default setting
5...500 s
5 s
2...250 s/h
2 s/h
0.10...60.0 s
0.10 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0...200°C
0°C
1...100 s
1 s
0.1...15.0 kΩ
0.1 kΩ
0.1...15.0 kΩ
0.1 kΩ