Technical Reference Manual
Table 10.-2Setting group 2
Variable
Checksum, SGR 1
Checksum, SGR 2
Checksum, SGR 3
Checksum, SGR 4
Checksum, SGR 5
Checksum, SGL 1
Checksum, SGL 2
Checksum, SGL 3
Checksum, SGL 4
Checksum, SGL 5
Checksum, SGL 6
Checksum, SGL 7
Checksum, SGL 8
Table 10.-3Control parameters
Description
PU scale (protected unit
scaling factor)
Rated frequency
Time setting range for
demand values in minutes
Non-volatile memory
settings
Time setting for disabling
new trip indications on the
LCD
Trip-circuit supervision
Sensor/thermistor
selection for input RTD1
Sensor selection for input
RTD2
Group/
Channel 2
Setting range
(R, W, P)
2S81
0...524287
2S82
0...524287
2S83
0...524287
2S84
0...524287
2S85
0...524287
2S91
0...1048575
2S92
0...1048575
2S93
0...1048575
2S94
0...1048575
2S95
0...1048575
2S96
0...1048575
2S97
0...1048575
2S98
0...1048575
Parameter
Setting range
(channel 0)
V103
0.50...2.50
V104
50 or 60 Hz
V105
0...999 min
V106
0...63
V108
0...999 min
V113
0 = not in use
1 = in use
V121
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
8 = PTC 0...20 kΩ
V122
0 = not in use
1 = Pt100 -45...+150°C
2 = Pt250 -45...+150°C
3 = Pt1000 -45...+150°C
4 = Ni100 -45...+250°C
5 = Ni120 -45...+250°C
6 = Cu10 -45...+150°C
7 = Ni120US -45...+250°C
1MRS 752263-MUM
Default
Customer's
setting
setting
6826
6826
0
9557
9557
4
8
0
0
0
0
0
0
Default
Customer's
setting
setting
1.00
50 Hz
10 min
63
60 min
0
0