ABB REM 610 Technical Reference Manual page 84

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

REM 610
84
Motor Protection Relay
Technical Reference Manual
Disturbance recorder
Table 4.1.15-4 Parameters for the disturbance recorder
Description
Remote triggering
Clear recorder memory
Sampling rate
Station identification/unit number
Rated frequency
Name of the motor drive
Digital channel texts
Analogue channel texts
Analogue channel
conversion factor and unit for I
Analogue channel
conversion factor and unit for the earth-fault
current
Internal trigger signals' checksum
Internal trigger signal's edge
Checksum of internal signal storing mask
Post-triggering recording length
External trigger signal's checksum
External trigger signal's edge
Checksum of external signal storing mask
Triggering state, clearing and restart
1)
The disturbance recorder requires this parameter to be set. The conversion factor is the
transformation ratio multiplied by the rated current of the relay. If this parameter has been given the
value 0, dashes will be shown on the LCD instead of the primary values and the recorded data will be
redundant.
2)
M1 can be used for broadcast triggering by using the unit address "900".
3)
Parameters can be written if the recorder has not been triggered.
4)
This value is copied to parameters M81 and M82.
Parameter
(channel 0)
2)
M1
M2
3)
M15
M18
M19
M20
M40...M47 R
M60...M63 R
1) 4)
M80
, I
and I
M81 and
L1
L2
L3
M82
1)
M83
V236
V237
3)
V238
V240
V241
V242
3)
V243
V246
1MRS 752263-MUM
R, W
Value
W
1
W
1
R, W
800/960 Hz
400/480 Hz
50/60 Hz
R, W
0...9999
R
50 or 60 Hz
R, W
Max 16 characters
R, W
Factor 0...65535, unit
(a, kA), e.g. 10 kA
R
R, W
Factor 0...65535, unit
(a, kA), e.g. 10 kA
R, W
0...8191
R, W
0...8191
R, W
0...8191
R, W
0...100%
R, W
0...31
R, W
0...31
R, W
0...31
R, W
R:
0 = recorder not
triggered
1 = recorder triggered
and recording stored
in the memory
W:
0 = clear recorder
memory
2 = download restart;
sets the first
information and the
time stamp for
triggering ready to be
read
4 = manual triggering

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents