ABB REM 610 Technical Reference Manual page 93

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

1MRS 752263-MUM
Motor protection Relay
Technical Reference Manual
Channel 0
Events always included in the event reporting:
Table 4.1.15.1-2 Event codes E1...E7
Channel Event Description
0
E1
IRF
0
E2
IRF disappeared
0
E3
Warning
0
E4
Warning disappeared
0
E5
Emergency start activated
0
E6
Emergency start deactivated
0
E7
The thermal level has been changed via serial
communication
Table 4.1.15.1-3 Event codes E50...E51
Channel Event Description
0
E50
Restart of relay
0
E51
Overflow of event buffer
Events possible to mask out:
Table 4.1.15.1-4 Event codes E31...E34
Channel Event Description
0
E31
Disturbance recorder triggered
0
E32
Disturbance recorder memory cleared
0
E33
HMI password opened
0
E34
HMI password closed
Default value of event mask V155
Channel 1
Table 4.1.15.1-5 Event codes E1...E14
Channel Event Description
1
E1
Motor start up begins
1
E2
Motor start up ends
Start of stage θ> activated
1
1)
E3
Start of stage θ> reset
1
1)
E4
1
E5
Alarm signal from stage θ> activated
Alarm signal from stage θ> reset
1
E6
Trip signal from stage θ> activated
1
E7
Trip signal from stage θ> reset
1
E8
Restart inhibit signal from stage θ> activated
1
E9
1
E10
Restart inhibit signal from stage θ> reset
Restart inhibit signal from stage Σt
1
E11
REM 610
Weighting
Default value
factor
1
2
4
8
Weighting
Default value
factor
1
2
4
8
16
32
64
128
256
512
activated 1024
si
1
0
0
0
1
0
0
1
0
1
0
1
0
0
0
0
93

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents