1MRS 752263-MUM
Motor protection Relay
Technical Reference Manual
Table 4.1.4.12-3 SGF2
Switch
Function
SGF2/1
Operation mode of the alarm indication of stage θ>
SGF2/2
Operation mode of the start indication of stage I
SGF2/3
Operation mode of the start indication of stage I>>
SGF2/4
Operation mode of the start indication of stage I<
SGF2/5
Operation mode of the start indication of stage I
SGF2/6
Operation mode of the start indication of stage I
SGF2/7
Operation mode of the alarm indication of stage ThA>
SGF2/8
Operation mode of the alarm indication of stageThB>
• 0 = the start indication will automatically be cleared once the
fault has disappeared
• 1 = latching. The start indication will remain active although
the fault has disappeared.
ΣSGF2
1)
In addition, the phase(s) which caused the start will be shown on the LCD.
Table 4.1.4.12-4 SGF3
Switch
Function
SGF3/1
Inhibition of stage I>>
SGF3/2
Inhibition of stage I<
SGF3/3
Inhibition of stage I
SGF3/4
Inhibition of stage I
SGF3/5
Inhibition of stage REV
• When the switch is in position 1, the stage is inhibited.
SGF3/6
Start-up supervision
• 0 = based on thermal stress calculation
• 1 = based on definite-time overcurrent protection
SGF3/7
Start criteria for stage I
• 0 = the stage will start when the conditions for motor start up
are met
• 1 = the stage will start when one or several phase currents
exceed the set start value
SGF3/8
Automatic doubling of the start value of stage I>>
• When the switch is in position 1, the set start value of the
stage will automatically be doubled at high inrush situations
ΣSGF3
>
0
>
2
2
x t
s
s
REM 610
Default
setting
0
1)
0
>
s
0
1)
0
1)
>
0
0
>
0
2
0
0
0
Default
setting
0
1
0
0
0
0
0
0
2
43