ABB REM 610 Technical Reference Manual page 72

Motor protection relay
Hide thumbs Also See for REM 610:
Table of Contents

Advertisement

REM 610
72
Motor Protection Relay
Technical Reference Manual
Table 4.1.14.2-5 Mapping of Modbus data
Description
UDR 4
UDR 5
UDR 6
UDR 7
UDR 8
UDR 9
UDR 10
UDR 11
UDR 12
UDR 13
UDR 14
UDR 15
UDR 16
Status registers
Status register 1
Status register 2
Status register 3
Analogue data
Phase current I
x I
L1
n
Phase current I
x I
L2
n
Phase current I
x I
L3
n
Earth-fault current x I
n
NPS current
Temperature from RTD1
Temperature from RTD2
Temperature from RTD3
Temperature from RTD4
Temperature from RTD5
Temperature from RTD6
Thermistor1,
resistance value
Thermistor 2,
resistance value
Digital data
Motor start up
Motor start up CD
Start signal from stage θ>
Start signal from stage θ>
CD
Alarm signal from stage θ>
Alarm signal from stage θ>
CD
Trip signal from stage θ>
Trip signal from stage θ> CD
Restart inhibit signal from
stage θ>
HR/IR
DI/Coil bit
address (.bit)
address
4 or 388
5 or 389
6 or 390
7 or 391
8 or 392
9 or 393
10 or 394
11 or 395
12 or 396
13 or 397
14 or 398
15 or 399
16 or 400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417.00
1
417.01
2
417.02
3
417.03
4
417.04
5
417.05
6
417.06
7
417.07
8
417.08
9
1MRS 752263-MUM
Value
Writeable
Comment
range
IRF code See Structure 1
Warning
See Structure 1
codes
See Structure 1
0...5000 0...50 x I
0...5000 0...50 x I
0...5000 0...50 x I
0...8000 0...800.0% I
0...5000 0...50 x I
-40...999 °C (signed)
-40...999 °C (signed)
-40...999 °C (signed)
-40...999 °C (signed)
-40...999 °C (signed)
-40...999 °C (signed)
0...200
0...20.0 kΩ
0...200
0...20.0 kΩ
0/1
1 = begins
0 = ends
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
0/1
1 = activated
n
n
n
n
n
1)
1)
1)
1)
1)
1)
2)
2)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents