5.7. PUMP PROTECTION

This option enables protection of the pumps/valves from blocking during long stand-still.
(usually during summer season when heating is off).
Activation of this option and setting of max. stand-still time of exits to the pumps/valves can be
set in menu: 5.Operation->5.7.Pump protection.
Factory set of max. stand-still time of the exits to the pumps/valves is 48 hours, ie. each 48 hours
of stand-still of the exit, exit will be started shortly.
5. Operation
1.
DHW / Heating
2.
Manual test
3.
Chimney sweep
4.
Forced shutdown
5.7.1. Pump protection
OFF
Technical instructions REGULATION PelTec / PelTec-lambda
5.
Flue pass. Cleaner
6.
Alarm
7.
Pump protection
8.
Internet supervision
Factory:
OFF
OFF
ON
Pump protection
shown only if WiFi box is installed
(additional equipment)
65