SPECIFICATIONS

2.5.1 Protection elements

The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated. FlexLogic
operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect with other
protection or control elements of the relay, building FlexLogic equations, or interfacing with other intelligent electronic
devices (IEDs) or power system devices via communications or different output contacts. If not specified, the operate times
given here are for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
2
PHASE/NEUTRAL/GROUND TOC
Current:
Pickup level:
Dropout level:
Level accuracy:
0.1 to 2.0 × CT:
> 2.0 × CT:
Curve shapes:
Curve multiplier:
Reset type:
Curve timing accuracy at 1.03 to 20 x pickup:
Voltage restraint:
PHASE/NEUTRAL/GROUND IOC
Pickup level:
Dropout level:
Level accuracy:
0.1 to 2.0 × CT rating:
> 2.0 × CT rating:
Overreach:
Pickup delay:
Reset delay:
Operate time:
Timer accuracy:
SENSITIVE DIRECTIONAL POWER
Measured power:
Number of stages:
Characteristic angle:
Calibration angle:
Minimum power:
Pickup level accuracy:
Hysteresis:
Pickup delay:
Timer accuracy:
Operate time:
PHASE UNDERVOLTAGE
Pickup level:
Dropout level:
Level accuracy:
Curve shapes:
2-20
Phasor or RMS
0.020 to 30.000 pu in steps of 0.001
97% to 98% of pickup
±0.5% of reading or ±0.4% of rated (whichever is greater)
±1.5% of reading > 2.0 × CT rating
IEEE Moderately/Very/Extremely Inverse; IEC (and BS) A/B/C and Short Inverse; GE IAC Inverse,
2
Short/Very/ Extremely Inverse; I
t; FlexCurves™ (programmable); Definite Time (0.01 s base
curve)
Time Dial = 0.00 to 600.00 in steps of 0.01
Instantaneous/Timed (per IEEE)
±3.5% of operate time or ±½ cycle (whichever is greater) from pickup to operate
Modifies pickup current for voltage in the range of 0.1 < V < 0.9 VT Nominal in a fixed linear rela-
tionship
0.020 to 30.000 pu in steps of 0.001
97 to 98% of pickup
±0.5% of reading or ±0.4% of rated (whichever is greater)
±1.5% of reading
<2%
0.00 to 600.00 s in steps of 0.01
0.00 to 600.00 s in steps of 0.01
<16 ms at 3 × pickup at 60 Hz (Phase/Ground IOC)
<20 ms at 3 × pickup at 60 Hz (Neutral IOC)
±3% of operate time or ±1/4 cycle (whichever is greater)
3-phase, true RMS
2
0 to 359° in steps of 1
0.00 to 0.95° in steps of 0.05
–1.200 to 1.200 pu in steps of 0.001
±1% or ±0.001 pu, whichever is greater
2% or 0.001 pu, whichever is greater
0 to 600.00 s in steps of 0.01
±3% of operate time or ±1/4 cycle (whichever is greater)
<50 ms
0.004 to 3.000 pu in steps of 0.001
102 to 103% of pickup
±0.5% of reading from 10 to 208 V
GE IAV Inverse;
Definite Time (0.1 s base curve)
CHAPTER 2: PRODUCT DESCRIPTION
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL