CONTROL ELEMENTS

5.8.6 Overfrequency (ANSI 81O)

SETTINGS  CONTROL ELEMENTS  OVERFREQUENCY  OVERFREQUENCY 1(4)
 OVERFREQUENCY 1
There are four overfrequency elements, numbered 1 through 4.
A frequency calculation for a given source is made on the input of a voltage or current channel, depending on which is
available. The channels are searched for the signal input in the following order: voltage channel A, auxiliary voltage
5
channel, current channel A, and ground current channel. The first available signal is used for frequency calculation.
The steady-state frequency of a power system is an indicator of the existing balance between the generated power and
the load. Whenever this balance is disrupted through the disconnection of significant load or the isolation of a part of the
system that has a surplus of generation, the effect is an increase in frequency. If the control systems of the generators do
not respond fast enough, to quickly ramp the turbine speed back to normal, the overspeed can lead to the turbine trip. The
overfrequency element can be used to control the turbine frequency ramp down at a generating location. This element
can also be used for feeder reclosing as part of the "after load shedding restoration."
The
OVERFREQ 1 SOURCE
The
OVERFREQ 1 PICKUP
5-264
OVERFREQ 1 FUNCTION:
Disabled
OVERFREQ 1 BLOCK:
Off
OVERFREQ 1 SOURCE:
SRC 1
OVERFREQ 1 PICKUP:
60.50 Hz
OVERFREQ 1 PICKUP
DELAY: 0.500 s
OVERFREQ 1 RESET
DELAY : 0.500 s
OVERFREQ 1 TARGET:
Self-reset
OVERFREQ 1 EVENTS:
Disabled
setting selects the source for the signal to be measured.
setting selects the level at which the overfrequency element is to pickup.
Figure 5-142: Overfrequency logic
Range: Disabled, Enabled
Range: FlexLogic operand
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 20.00 to 65.00 Hz in steps of 0.01
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS