GE C60 Instruction Manual page 335

Breaker protection system
Hide thumbs Also See for C60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
The C60 is provided with this optional feature, specified as an option at the time of ordering. Using the order
code for your device, see the order codes in chapter 2 for details.
User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The
number depends on the front panel ordered.
Enhanced horizontal front panel — 16 user-programmable pushbuttons
Enhanced vertical front panel — 6 user-programmable pushbuttons
Standard horizontal front panel — 12 user-programmable pushbuttons
Graphical front panel — 16 user-programmable pushbuttons (eight physical pushbuttons, eight graphical interface
pushbuttons)
User-programmable pushbuttons require a front panel with that option. If the front panel was ordered separately,
update the EnerVista software under Maintenance > Change Front Panel.
The digital state can be entered locally (by directly pressing the front panel pushbutton or optional graphical front panel
interface) or remotely (via FlexLogic operands) into FlexLogic equations, protection elements, and control elements. Typical
applications include breaker control, autorecloser blocking, and setting groups changes. For example, set pushbuttons 1 to
5 to select settings groups 1 to 5, or set pushbutton 1 to clear event records. The user-programmable pushbuttons are
under the control level of password protection.
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
PUSHBTN 1 ON TEXT:
PUSHBTN 1 OFF TEXT:
PUSHBTN 1 HOLD:
0.0 s
PUSHBTN 1 SET:
Off
PUSHBTN 1 RESET:
Off
PUSHBTN 1 AUTORST:
Disabled
PUSHBTN 1 AUTORST
DELAY: 1.0 s
PUSHBTN 1 REMOTE:
Off
PUSHBTN 1 LOCAL:
Off
PUSHBTN 1 DROP-OUT
TIME: 0.00 s
PUSHBTN 1 LED CTL:
Off
PUSHBTN 1 MESSAGE:
Disabled
PUSHBUTTON 1
EVENTS: Disabled
Range: up to 20 alphanumeric characters
Range: up to 20 alphanumeric characters
Range: 0.0 to 10.0 s in steps of 0.1
Range: FlexLogic operand
Range: FlexLogic operand
Range: Disabled, Enabled
Range: 0.2 to 600.0 s in steps of 0.1
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 60.00 s in steps of 0.05
Range: FlexLogic operand
Range: Disabled, Normal, High Priority
Range: Disabled, Enabled