15.
Appendix 8. Firmware upgrade
Bellow are given the steps for firmware upgrade of the DAEnetIP2 with
DAEnetIP Burner:
1. Download and save the version you need for upgrading the. The binary (.bin)
file must be downloaded from this
2. Navigate the DAEnetIP Burner application to this file by clicking button with
label "...".
3. From the Device list select DAEnetIP2.
4. In the IP address field type the IP address of the DAEnetIP2 controller that
must be upgraded. By default it is 172.16.100.2.
5. In the Port field type the target port on that DAEnetIP2 can be reached. This
is the SNMP port. By default it is 161.
6. In the Password field type the SNMP password used in this DAEnetIP2
controller. By default it is "private"
7. Check if the settings are correct by clicking button "Check device". After
successful connection under this button it must appears text with the
DAEnetIP2 version. If this not happens it means the connection is not
successful and you must repeat again steps 3-7.
8. Set the TFTP Server. This is usually the IP of the user's computer.
9. Set the maximum retries field. This field shows how many times
the DAEnetIP Burner will try to reconnect with the DAEnetIP2 controller if the
connection is lost for a moment. A value of 5-10 is reasonable.
10. Start update by clicking Burn button. If everything is correct, a new line must
appear in the event log and the progress bar must starts moving on.
link
Figure 37. DAEnetIP Burner
DAEnetIP2 User Manual
12 Sep 2013
-48-