Checking Profibus PA
VEGABAR 51 • Profibus PA
The hotline is available to you 7 days a week round-the-clock. Since
we offer this service world-wide, the support is only available in the
English language. The service is free of charge, only the standard
telephone costs will be charged.
?
When an additional instrument is connected, the segment fails.
Max. supply current of the segment coupler exceeded
l
à Measure the current consumption, reduce size of segment
?
Wrong presentation of the measured value in Simatic S5
Simatic S5 cannot interpret the number format IEEE of the
l
measured value
à Insert converting component from Siemens
?
In Simatic S7 the measured value is always presented as 0
Only four bytes are consistently loaded in the PLC
l
à Use function component SFC 14 to load 5 bytes consistently
?
Measured value on the indicating and adjustment module does not
correspond to the value in the PLC
The menu item "Display - Display value" is not set to "PA-Out"
l
à Check values and correct, if necessary
?
No connection between PLC and PA network
Incorrect adjustment of the bus parameter and the segment
l
coupler-dependent baud rate
à Check data and correct, if necessary
?
Instrument does not appear during connection setup
Profibus DP cable pole-reversed
l
à Check cable and correct, if necessary
Incorrect termination
l
à Check termination at the beginning and end points of the bus
and terminate, if necessary, according to the specification
Instrument not connected to the segment, double assignment
l
of an address
à Check and correct, if necessary
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
8 Maintenance and fault rectification