Operating Instructions Manual as well as the Safety Manual that comes with instruments with SIL qualification. These manuals are available in the download area of "www.vega.com". Operating instructions VEGABAR 82 - Slave sensor for elec- tronic differential pressure with SIL qualification: Document-ID 48046 Safety Manual VEGABAR series 80 - Two-wire 4 …...
During work on and with the device, the required personal protective equipment must always be worn. Appropriate use VEGABAR 82 is a slave sensor for electronic differential pressure measurement. You can find detailed information about the area of application in chapter "Product description".
(see chapter "Technical Data"). In addition, a temperature derating of the process fitting, e. g. with flanges, can limit the permissible process pressure range according to the respective standard. VEGABAR 82 • Slave sensor for electronic differential pressure...
Alternatively, you can access the data via your smartphone: • Download the VEGA Tools app from the "Apple App Store" or the "Google Play Store" • Scan the Data Matrix code on the type label of the instrument or •...
Instruments with absolute pressure Combination Master - Slave In principle, any sensor combination within the instrument series is allowed. The following requirements must be fulfilled: • Configuration, Master sensor suitable for electronic differential pressure VEGABAR 82 • Slave sensor for electronic differential pressure...
Page 7
Static pressure: 0.8 bar Differential pressure on orifice: 50 mbar = 0.050 bar Total pressure: 0.8 bar + 0.05 bar = 0.85 bar Instrument selection Nominal measuring range Master: 1 bar VEGABAR 82 • Slave sensor for electronic differential pressure...
Page 8
Slave (static or superimposed pressure) are output by the sensor. Depending on the instrument version, output as 4 … 20 mA signal or digitally via HART, Profibus PA or Foundation Fieldbus. VEGABAR 82 • Slave sensor for electronic differential pressure...
Fig. 3: Connection steps 5 and 6 5. Insert the wire ends into the terminals according to the wiring plan 6. Check the hold of the wires in the terminals by lightly pulling on them VEGABAR 82 • Slave sensor for electronic differential pressure...
Ground terminal for connection of the cable screening Connect shielding here. Connect ground terminal on the outside of the hous- ing to ground as prescribed. The two terminals are galvanically connected. VEGABAR 82 • Slave sensor for electronic differential pressure...
The display and adjustment module is powered by the sensor, an ad- ditional connection is not necessary. Fig. 6: Installing the display and adjustment module in the electronics compart- ment of the single chamber housing VEGABAR 82 • Slave sensor for electronic differential pressure...
For each parameter change you have to enter the PIN of the instru- ment. In delivery status, the PIN is "0000". Change parameters You can find a description below the respective parameter. VEGABAR 82 • Slave sensor for electronic differential pressure...
Page 14
4. Depending on the application, carry out the adjustment e.g. in the menu items "Min. adjustment" and "Max. adjustment". Parameterization example VEGABAR 82 always measures pressure independently of the pro- cess variable selected in the menu item "Application". To output the selected process variable correctly, an allocation of the output signal to 0 % and 100 % must be carried out (adjustment).
Page 15
Afterwards you confirm that the serial number of your instrument was carried over correctly. This is used to check device communication. 4. Verify parameters Confirm the modified values one after the other. VEGABAR 82 • Slave sensor for electronic differential pressure...
≤ 3.6 mA Current output - Min./ 3.8 mA Max. 20.5 mA Lock adjust- Last setting ment (SIL) Display Menu item Default setting Menu language Order-specific Displayed value 1 Current output in % VEGABAR 82 • Slave sensor for electronic differential pressure...
Page 17
0.00 % correspond to 0.00 m 100.00 %, 1 m Info Menu item Parameter Device name VEGABAR 82 Instrument version Hardware and software version Factory calibration Date date Sensor characteristics Order-specific characteristics VEGABAR 82 • Slave sensor for electronic differential pressure...
< 0.05 Ω/m (0.015 Ω/ft) Voltage supply for the complete system through Master Operating voltage Ʋ U 12 V DC B min IP 66/IP 68 (0.2 bar), only with absolute pressure. VEGABAR 82 • Slave sensor for electronic differential pressure...
Page 19
6 Supplement Ʋ U with lighting switched on 16 V DC B min Ʋ U Depending on signal output and version of the master B max sensor VEGABAR 82 • Slave sensor for electronic differential pressure...