Section 7
Troubleshooting
7.2.2
84
Fault indication
Internal Fault
Conf. error,X130
Internal Fault
Card error,X000
Internal Fault
Card error,X100
Internal Fault
Card error,X110
Internal Fault
Card error,X120
Internal Fault
Card error,X130
Internal Fault
LHMI module
Internal Fault
RAM error
Internal Fault
ROM error
Internal Fault
EEPROM error
Internal Fault
FPGA error
Internal Fault
RTC error

Warnings

A fault indication message, which includes text Warning with additional text, a
code, date and time, is shown on the LHMI to indicate the fault type. If more than
one type of fault occur at the same time, indication of the latest fault is displayed on
the LCD. The fault indication message can be manually cleared.
When a fault appears, the fault indication message is to be recorded and stated when
ordering service.
Fault code
Additional information
66
Card in slot X130 is wrong type, is missing
or does not belong to the original
composition.
72
Card in slot X000 is faulty.
73
Card in slot X100 is faulty.
74
Card in slot X110 is faulty.
75
Card in slot X120 is faulty.
76
Card in slot X130 is faulty.
79
LHMI module is faulty. The fault indication
may not be seen on the LHMI during the
fault.
80
Error in the RAM memory on the CPU
card.
81
Error in the ROM memory on the CPU
card.
82
Error in the EEPROM memory on the CPU
card.
83
Error in the FPGA on the CPU card.
84
Error in the RTC on the CPU card.
1MRS756708 A