1MRS750532-MUM Bus Connection Module RER 103 Issued: 11.03.1997 Version: E/17.01.2007 Technical Descriptiopn Contents 1. General ..................5 2. Principle of operation ...............6 3. Construction ................7 4. Type designation ..............8 5. Fibre-optic connectors and technical data ......9...
Page 3
This document and parts thereof must not be reproduced or copied without written permission from ABB Oy, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose.
1MRS750532-MUM Product Description Sub Title Manual Type General The bus connection module RER 103 acts as an interfacing unit between an RE_ 500 ® device and the fibre-optic SPA, LON and IEC 60870-5-103 bus. The bus ® connection module converts incoming optical signals from the SPA, LON IEC_103 bus to electrical RS-485 signals for the RE_ 500 devices and vice versa.
Technical Description Principle of operation The RER 103 Bus Connection Module can be used in Loop and Star type bus topologies. Also the line idle state of the module is selectable. It can be light on or off. The selection of Loop/Star and light on/off is made by jumpers.
Sub Title Manual Type Construction The bus connection module RER 103 consists of a printed circuit board and is housed in a plastic case. The incoming optical fibre is connected to the receiver input Rx and the outgoing optical fibre to the transmitter output Tx. Special attention must be paid to the handling, mounting, connection, etc.
Table 5.-2 Technical data Powered from host device (5V dc) Auxiliary power supply ~ 0.4 W Max Burden 1.25 Mbps Max data transfer rate RER 103 Width: 35.0 mm Mechanical dimensions Height: 73.0 mm Depth: 20.0 mm -10...55°C Operating temperature range -40...70°C...
Page 9