Serial Link Diagnostics And Monitoring - ABB REF615 Operation Manual

615 series
Hide thumbs Also See for REF615:
Table of Contents

Advertisement

1MRS756708 A
8.5.1.2
615 series
Operation Manual
COM parameter
Serial mode
CTS Delay
RTS Delay
Baudrate
1) When fiber mode is used, the
In addition to setting the COM parameter, a communication card with
many hardware options may also require changing the jumpers on the
communication card.
Connection of a serial communication protocol to a specific serial port
The serial communication protocol (instance) settings include a setting parameter
called Serial port n (n = protocol instance number). Setting options for this parameter
are COM1, COM2 and so on. Select the desired serial port for the protocol instance
through this parameter.
All link setting parameters are not found in the COMn settings.
Additional link setting parameters are found in the setting parameter
list of the used serial protocol, since some serial protocol standards
allow changes in link parameters, while other protocol standards do
not.

Serial link diagnostics and monitoring

Serial communication diagnostics and monitoring is divided between the serial link
driver and the serial communication protocol. The lower level physical and protocol-
independent aspects of the UART-based serial communication are monitored in the
Values
0 = RS485 2wire
1 = RS485 4wire
2 = RS232 no handshake
3 = RS232 with handshake
0...60000 [ms]
0...60000 [ms]
1 = 300
2 = 600
3 = 1200
4 = 2400
5 = 4800
6 = 9600
7 = 19200
8 = 38400
9 = 57600
10 = 115200 [bits/sec]
Serial mode parameter value must be RS485 2wire .
Section 8
Commissioning
1)
Hardware options
For galvanic modes. RS-type depends
on the communication card used.
Note that this setting parameter is
Fiber mode is set to No
relevant only if
Fiber .
RS232 mode only
RS232 mode only
All modes
99