ABB REF615 Operation Manual page 108

615 series
Hide thumbs Also See for REF615:
Table of Contents

Advertisement

Section 8
Commissioning
100
serial link driver. Diagnostic counters and monitoring values are found via the LHMI
in Monitoring/Communication/COMn (n= 1,2,...).
Depending on the communication protocol, the serial driver software receives single
characters or complete protocol frames, based on the frame start/stop characters or
on timing.
Monitoring data for a COM channel can be divided into basic and detailed diagnostic
counters.
Table 20:
Monitoring data for a COM channel
Parameter
Range
Characters
0...2147483646
received
Frames received
0...2147483646
Frames discarded
0...2147483646
Frames
0...2147483646
transmitted
CD Lost
0...2147483646
Collision
0...2147483646
CTS Timeout
0...2147483646
Transmission
0...2147483646
timeout
Parity errors
0...2147483646
Overrun errors
0...2147483646
Framing errors
0...2147483646
Link status
1
Whether all diagnostic counters are relevant depends on the communication hardware
and communication protocol.
Type
Description
Basic
Number of separate characters received.
Basic
Number of successfully received complete
frames.
Basic
Number of frames discarded.
Basic
Number of frames transmitted.
Detailed
Number of carrier-detect signal lost during
receive.
Detailed
Number of collisions detected.
Detailed
Number of clear-to-send signal timeout
errors.
Detailed
Number of transmission timeout errors.
Detailed
Number of character parity errors detected.
Detailed
Number of character overrun errors
detected.
Detailed
Number of character overrun errors
detected.
1 = Reset counters (by entering 1 the
diagnostic counters are reset)
1MRS756708 A
615 series
Operation Manual

Advertisement

Table of Contents
loading

Table of Contents