Section 7
Troubleshooting
7.2.3
7.3
7.3.1
7.3.2
7.3.3
86
Warning indication
Warning
ARC1 cont. light
Warning
ARC2 cont. light
Warning
ARC3 cont. light

LED and display messages

Usually when a LED is lit, an indication is shown on the LHMI and event 10 is
generated.

Correction procedures

Rebooting software

1.
Select Main menu/Configuration/General/Software reset and press
2.
Change the value with

Restoring factory settings

In case of configuration data loss or any other file system error that prevents the IED
from working properly, the whole file system can be restored to the original factory
state. All default settings and configuration files stored in the factory are restored.
1.
Select Main menu/Configuration/General/Factory setting and press
2.
Set the value with
3.
Confirm by selecting Yes with
The IED restores the factory settings and restarts. Restoring takes 1-3 minutes.
Confirmation of restoring the factory settings is shown on the display a few seconds,
after which the IED restarts.

Setting password

If user authorization is off or the user is logged in as an administrator, user passwords
can be set via the LHMI or WHMI or with PCM600.
The password can be set to write mode with engineer or operator
rights but the changes to the password are not saved.
Warning code
Additional information
85
A continuous light has been detected on
the ARC light input 1.
86
A continuous light has been detected on
the ARC light input 2.
87
A continuous light has been detected on
the ARC light input 3.
or
and press
or
and press
or
and press
1MRS756708 A
.
.
again
Operation Manual
.
.