Introduction
This chapter describes how to install the 4007ES panel. It can be semi-flush or surface mount.

3.1 Mounting the 4007ES panels

• Due to the danger of metal fragments falling into electronics when drilling the holes for the conduits, remove the electronics in the system:
- To remove the electronics, unscrew the ten screws. Remove the power supply and store it in a safe, clean, and dry location until the panel
installation is completed, see Figure 2: Screws location on page 6.
- If installing a 4007ES hybrid panel, also remove the Zone/Relay card (three screws).
• Use a suitable punch where a conduit entrance is required. The knockouts are not provided. Locate and create on-site as required during installation.
Fig 2: Screws location
• For surface or semi-flush mounting to a wooden wall structure, the panel must be attached with four 1 1/2 in. (38 mm) long lag bolts and four 1/2 in.
(13 mm) diameter washers, supplied by others.
• For surface mounting, secure the box to the wall using the tear-drop mounting holes on the back surface. For semi-flush mounting, secure the box
along the sides to the wall studs. Note that the front surface of the back box must protrude at least 1-1/2 in. (38mm) from the wall surface for semi-
flush installation. A trim kit is supplied for semi-flush mounting, see the
• To install the panel, see Figure 3: Back Box Installation dimensions and Semi-Flush Mounting (Right) on page 7 for the dimensions and use the
holes in the back box to secure it to the wall.
Page 6
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Trim kit application
on page 7 section for more information.