2.2 Glossary

Table 3: Glossary
Term
Aux
EOL
FACP
Hybrid
IDC
IDNet
IDNet+
IDNAC
NAC
NIC
Regulated 24 DC
RS-232 module
RUI
Simple NAC
SLC
SmartSync
User interface The user interface is a 4.3 in. (109mm) diagonal color LCD with a built-in resistive touch panel and 12 indicating LEDs. The color LCD
provides system status and access to perform system functions and to change the system configuration.
Figure 1: 4007ES panel inside view on page 5 shows an inside view of the 4007ES panel with the optional LED module (4007-9805) installed.
Page 5
Definition
Abbreviation for Auxiliary; typically used to describe Auxiliary Power.
End-of-Line, typically in reference to and end-of-line resistor or EOL
resistor.
Fire Alarm Control Panel.
In this document, "Hybrid" the 4007ES Hybrid models that provide both
addressable and conventional initiation with conventional non addressable Notification Appliance Circuits.
Initiating Device Circuit.
Addressable SLC for up to 250 addressable devices.
IDNet which is electrically isolated from internal panel electronics.
Individual Device Notification Appliance Circuit (Addressable).
Notification Appliance Circuit, formerly called signal circuit.
Network Interface Card for the 4120 network.
Notification appliance operation that meets the minimum listing
requirements; inrush currents typically require power supply and NAC rating.
The Dual RS-232 interface module provides a serial communication
interface to an AC or DC printer, a PC Annunciator, or a third party computer.
Remote Unit Interface; SLC for communications with remote
annunciators.
A Reverse Polarity Supervised Notification Appliance Circuit that is
capable of on steady or coded operation. Sync or SmartSync operation is not supported.
Signaling Line Circuit
A reverse polarity monitored NAC capable of synchronizing and
controlling both horns and strobes on the same circuit using a proprietary signaling protocol. Used as the
protocol for TrueAlert Non-Addressable Devices.
Fig 1: 4007ES panel inside view