6.8 Auxiliary power selection

AUX PWR/SNAC overview
The AUX PWR/SNAC terminal block is located on the top left corner of the power supply. Using the ES Panel Programmer, this point can be configured
as either a 24V Auxiliary (AUX) power or as a simple reverse polarity Notification Appliance Circuit (NAC). This circuit does not support TrueAlert
addressable devices nor non-addressable SmartSync appliances.
The AUX PWR/SNAC is rated 2 A maximum. The current used is deducted from the total available power supply current.
Output rating:
Current Rating:
Earth Detection
Threshold
Wiring Gauge:
Wiring Notes:
1. All wiring from the AUX/SNAC is power limited.
2. The conductors must test free of all grounds and stray voltages before connection to appliances and panel.
3. Terminate Class B NACs, as shown, using a 733- 894 EOL. For Canadian applications, mount end-of-line resistor to a Simplex-US Model 431537
EOL plate in accordance with ULC-S527.
4. If the wiring is routed outside the building, use of a listed secondary protector is required. Use Simplex2081-9028 (rated 5 A) or 2081-9044 (rated
0.2 A). A protector must be installed at each building exit or entrance. Each 2081-9028 adds 0.2 ohms wiring resistance. 2081-9044 adds 6 ohms
wiring resistance, and greatly reduces the wiring distance.
Table 25: Simple NAC wiring limits
Alarm current
20 AWG
0.25
617 ft
0.50
308 ft
0.75
206 ft
1.00
154 ft
1.25
123 ft
1.50
103 ft
1.75
88 ft
Page 33
Fig 27: AUX/SNAC
terminal
29.5 V maximum
2 A, maximum.
10K ohms minimum from either positive
or negative terminals.
18 AWG (min.)
to 12 AWG (max.).
Fig 28: Simple NAC wiring
18 AWG
16AWG
981 ft
1560 ft
490 ft
780 ft
327 ft
520 ft
245 ft
390 ft
196 ft
312 ft
163 ft
260 ft
140 ft
223 ft
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
14 AWG
12 AWG
2480 ft
3944 ft
1240 ft
1972 ft
827 ft
1315 ft
620 ft
986 ft
496 ft
789 ft
413 ft
657 ft
354 ft
563 ft
Line resistance (Ohms)
14.00
7.00
4.67
3.50
2.80
2.33
2.00