5.5 IDNAC Class B wiring tables

Use the following tables to calculate the wiring distance to farthest appliance. The maximum wiring distance is the shorter of the distance limits as
calculated by alarm current voltage drop or by reaching the communications distance limit.
Wiring Limit Based on Alarm Current
Alarm
Current
0.050
0.100
0.150
0.200
0.250
0.300
0.350
0.400
0.450
0.500
0.750
1.000
1.250
1.500
1.750
2.000
2.250
2.500
2.750
3.000
Wiring distance must not exceed 4000 ft
Fig 17: Class B wiring tables
NOTE:
Although the required wiring for IDNAC circuits is twisted pair (controlled impedance) wiring, some applications will wish to take
advantage of existing wiring that is not twisted pair. This is only allowed if both conductors of the IDNAC circuit reside in the same metal conduit,
and only under certain conditions. Check with your local sales office before using wiring that is not twisted pair.
Page 20
Distance to the Last Appliance
20
18
16
14
AWG
AWG
AWG
AWG
AWG
4000 ft
4000 ft 4000 ft 4000 ft 4000 ft
2644 ft
4000 ft 4000 ft 4000 ft 4000 ft
1763 ft
2802 ft 4000 ft 4000 ft 4000 ft
1322 ft
2102 ft
3342
4000 ft 4000 ft
1058 ft
1681 ft 2674 ft 4000 ft 4000 ft
881 ft
1401 ft
2228 ft
3542 ft 4000 ft
755 ft
1201 ft 1910 ft 3036 ft 4000 ft
661 ft
1051 ft 1671 ft 2657 ft
4000 ft
588 ft
934 ft
1485 ft 2362 ft
3756
529 ft
841 ft
1337 ft
2125 ft
3380
353 ft
560 ft
891 ft
1417 ft
2254 ft
264 ft
420 ft
668 ft
1063 ft
1690 ft
212 ft
336 ft
535 ft
850 ft
1352 ft
176 ft
280 ft
446 ft
708 ft
1127 ft
151 ft
240 ft
382 ft
607 ft
966 ft
132 ft
210 ft
334 ft
531 ft
845 ft
118 ft
187 ft
297 ft
472 ft
751 ft
106 ft
168 ft
267 ft
425 ft
676 ft
96 ft
153 ft
243 ft
386 ft
615 ft
88 ft
140 ft
223 ft
354 ft
563 ft
Ohms per 1000
ft
Gage
Ohms/1000 ft
20 AWG
11.347
18 AWG
7.137
16 AWG
4.488
14 AWG
2.8230
12 AWG
1.7750
4007ES and 4007ES Hybrid Fire Alarm Systems Installation Manual
Wiring Limit Based on Communication
Line
Impedance
Devices
12
(Ohms)
14.54
1
1252 ft
12.96
5
1142 ft
11.38
10
1003 ft
10.14
15
9.12
20
8.28
25
7.58
30
6.97
35
6.45
40
6.00
45
5.60
50
5.24
55
4.92
60
4.75
63
4.64
65
4.38
70
4.15
75
3.94
80
3.74
85
3.56
90
3.40
95
3.24
100
3.10
105
2.97
110
2.85
115
2.73
120
2.58
127
Wiring distance must not exceed 4000 ft
Distance to the Last Appliance
20
18
16
14
AWG
AWG
AWG
AWG
2038 ft
3241 ft
4000 ft
1815 ft
2887 ft
4000 ft
1595 ft
2536 ft
4000 ft
893 ft
1420 ft
2258 ft
3590 ft
804 ft
1278 ft
2033 ft
3231ft
730 ft
1160 ft
1845 ft
2934 ft
668 ft
1061 ft
1688 ft
2683 ft
614 ft
977 ft
1553 ft
2469 ft
568 ft
904 ft
1437 ft
2285 ft
528 ft
840 ft
1336 ft
2124 ft
493 ft
784 ft
1247 ft
1982 ft
462 ft
734 ft
1168 ft
1856 ft
434 ft
690 ft
1097 ft
1744 ft
419 ft
665 ft
1058 ft
1682 ft
409 ft
650 ft
1034 ft
1643 ft
386 ft
614 ft
976 ft
1552 ft
366 ft
581 ft
924 ft
1469 ft
347 ft
551 ft
877 ft
1394 ft
2217 ft
330 ft
524 ft
833 ft
1325 ft
314 ft
499 ft
794 ft
1262 ft
299 ft
476 ft
757 ft
1203 ft
286 ft
454 ft
723 ft
1149 ft
273 ft
435 ft
691 ft
1099 ft
262 ft
416 ft
662 ft
1052 ft
251 ft
399 ft
634 ft
1009 ft
241 ft
383 ft
609 ft
968 ft
228 ft
362 ft
576 ft
915 ft
12
AWG
4000 ft
4000 ft
4000 ft
4000 ft
4000 ft
4000 ft
4000 ft
3928 ft
3634 ft
3378 ft
3152 ft
2952 ft
2774 ft
2675 ft
2613 ft
2468 ft
2337 ft
2107 ft
2006 ft
1913 ft
1827 ft
1748 ft
1673 ft
1604 ft
1539 ft
1456 ft