5.2 PRODUCT SETUP
An event is logged in the event record (as per user setting) when a control pushbutton is pressed. No event is logged when
the pushbutton is released. The faceplate keys (including control keys) cannot be operated simultaneously – a given key
must be released before the next one can be pressed.
The control pushbuttons become user-programmable only if the breaker control feature is not configured for manual control
via the USER 1 through 3 pushbuttons as shown below. If configured for manual control, breaker control typically uses the
larger, optional user-programmable pushbuttons, making the control pushbuttons available for other user applications.
SETTING
CONTROL PUSHBUTTON
{
1 FUNCTION:
Enabled=1
SETTINGS
SYSTEM SETUP/
BREAKERS/BREAKER 1/
BREAKER 1 PUSHBUTTON
CONTROL
Enabled=1
SYSTEM SETUP/
BREAKERS/BREAKER 2/
BREAKER 2 PUSHBUTTON
CONTROL
Enabled=1
5
5-82
:
AND
RUN
OFF
ON
:
Figure 5–13: CONTROL PUSHBUTTON LOGIC
F60 Feeder Protection System
TIMER
FLEXLOGIC OPERAND
0
CONTROL PUSHBTN 1 ON
100 msec
5 SETTINGS
842010A2.CDR
GE Multilin