6.2 STATUS
PATH: ACTUAL VALUES
 INCIPIENT FAULT 1
The number of detected incipient faults for each incipient fault element are displayed here for each phase. These values
can be reset to zero with the
PATH: ACTUAL VALUES
 COMM STATUS
 REMAINING CONNECT
6
These values specify the remaining number of TCP connections still available for each protocol. The display depends on
the options applicable to your device, for example the PMU entry does not display when not applicable. Each time a con-
nection is used, the remaining number of connections decrements. When released, the remaining number of connections
increments. If no connection is made over the specific protocol, the number equals the maximum number available for the
specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus
TCP status shows 4.
— The number of IEC 61850 connections remaining.
MMS TCP
— The maximum number of PMU TCP connections matches the number of aggregators. The maximum number
PMU TCP
of aggregators for the N60 is 4. The maximum number for the C60 is 2. The maximum number is 1 for other products with
a PMU. The remaining number of aggregators displays here.
The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation net-
works.
6-12

STATUS
INCIPIENT FAULT
INCIPIENT FAULT 1
PH A FAULTS: 0
INCIPIENT FAULT 1
MESSAGE
PH B FAULTS: 0
INCIPIENT FAULT 1
MESSAGE
PH C FAULTS: 0

COMMANDS
CLEAR RECORDS

STATUS
COMM STATUS REMAINING CONNECT
MMS TCP(max 5)
5
MODBUS TCP(max 4)
MESSAGE
4
DNP TCP (max 2)
MESSAGE
2
IEC-104 (max 2)
MESSAGE
2
PMU TCP
MESSAGE
1
F60 Feeder Protection System
INCIPIENT FAULT 1(2)
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1
Range: 0 to 65535 in steps of 1

CLEAR INCIPENT FAULT COUNTERS

6.2.22 REMAINING CONNECTION STATUS

Range: 0 to 5
Range: 0 to 4
Range: 0 to 2
Range: 0 to 2
Range: 1 to 4

6.2.23 PARALLEL REDUNDANCY PROTOCOL (PRP)

6 ACTUAL VALUES

6.2.21 INCIPIENT FAULT DETECTOR

command.