B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 42 of 70)
ADDR
REGISTER NAME
8610
Breaker Failure 1 Timer 3 Pickup
8611
Breaker Failure 1 Breaker Status 1 Phase A/3P
8613
Breaker Failure 1 Breaker Status 2 Phase A/3P
8615
Breaker Failure 1 Breaker Test On
8617
Breaker Failure 1 Phase Amp Hiset Pickup
B
8618
Breaker Failure 1 Neutral Amp Hiset Pickup
8619
Breaker Failure 1 Phase Amp Loset Pickup
861A
Breaker Failure 1 Neutral Amp Loset Pickup
861B
Breaker Failure 1 Loset Time
861C
Breaker Failure 1 Trip Dropout Delay
861D
Breaker Failure 1 Target
861E
Breaker Failure 1 Events
861F
Breaker Failure 1 Phase A Initiate
8621
Breaker Failure 1 Phase B Initiate
8623
Breaker Failure 1 Phase C Initiate
8625
Breaker Failure 1 Breaker Status 1 Phase B
8627
Breaker Failure 1 Breaker Status 1 Phase C
8629
Breaker Failure 1 Breaker Status 2 Phase B
862B
Breaker Failure 1 Breaker Status 2 Phase C
862D
...Repeated for Breaker Failure 2
FlexState Settings (Read/Write Setting)
8800
FlexState Parameters (256 items)
Digital Elements (Read/Write Setting) (48 modules)
8A00
Digital Element 1 Function
8A01
Digital Element 1 Name
8A09
Digital Element 1 Input
8A0B
Digital Element 1 Pickup Delay
8A0D
Digital Element 1 Reset Delay
8A0F
Digital Element 1 Block
8A11
Digital Element 1 Target
8A12
Digital Element 1 Events
8A13
Digital Element 1 Pickup LED
8A14
Reserved (2 items)
8A16
...Repeated for Digital Element 2
8A2C
...Repeated for Digital Element 3
8A42
...Repeated for Digital Element 4
8A58
...Repeated for Digital Element 5
8A6E
...Repeated for Digital Element 6
8A84
...Repeated for Digital Element 7
8A9A
...Repeated for Digital Element 8
8AB0
...Repeated for Digital Element 9
8AC6
...Repeated for Digital Element 10
8ADC
...Repeated for Digital Element 11
8AF2
...Repeated for Digital Element 12
8B08
...Repeated for Digital Element 13
8B1E
...Repeated for Digital Element 14
8B34
...Repeated for Digital Element 15
8B4A
...Repeated for Digital Element 16
8B60
...Repeated for Digital Element 17
8B76
...Repeated for Digital Element 18
8B8C
...Repeated for Digital Element 19
8BA2
...Repeated for Digital Element 20
8BB8
...Repeated for Digital Element 21
8BCE
...Repeated for Digital Element 22
B-50
RANGE
0 to 65.535
0 to 4294967295
0 to 4294967295
0 to 4294967295
0.001 to 30
0.001 to 30
0.001 to 30
0.001 to 30
0 to 65.535
0 to 65.535
0 to 2
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
---
0 to 4294967295
0 to 999999.999
0 to 999999.999
0 to 4294967295
0 to 2
0 to 1
0 to 1
---
F60 Feeder Protection System
APPENDIX B
UNITS
STEP
FORMAT
s
0.001
F001
---
1
F300
---
1
F300
---
1
F300
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
s
0.001
F001
s
0.001
F001
---
1
F109
---
1
F102
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F102
---
---
F203
"Dig Element 1"
---
1
F300
s
0.001
F003
s
0.001
F003
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
---
F001
DEFAULT
0
0
0
0
1050
1050
1050
1050
0
0
0 (Self-reset)
0 (Disabled)
0
0
0
0
0
0
0
0
0 (Disabled)
0
0
0
0
0 (Self-reset)
0 (Disabled)
1 (Enabled)