GE F60 Instruction Manual page 593

Ur series. feeder protection system
Hide thumbs Also See for F60:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 47 of 70)
ADDR
REGISTER NAME
A006
On Load Time Before Reset 1
A008
Cold Load Pickup 1 Source
A009
Cold Load Pickup 1 Reserved
A00A
...Repeated for Cold Load Pickup 2
VT Fuse Failure (Read/Write Setting) (4 modules)
A09A
VT Fuse Failure1 Function
A09B
VT Fuse Failure Neutral Wire Open1 Function
A09C
VT Fuse Failure Neutral Wire Open 1 3rd Harmonic Pickup
A09D
...Repeated for module number 2
A0A0
...Repeated for module number 3
A0A3
...Repeated for module number 4
VT Fuse Failure Actuals (Read Only) (4 modules)
A0AC
VT Fuse Failure 1 V0 3rd Harmonic
A0AE
...Repeated for module number 2
A0B0
...Repeated for module number 3
A0B2
...Repeated for module number 4
Selector Switch Actual Values (Read Only)
A210
Selector Switch 1 Position
A211
Selector Switch 2 Position
Selector Switch Settings (Read/Write) (2 modules)
A280
Selector 1 Function
A281
Selector 1 Range
A282
Selector 1 Timeout
A283
Selector 1 Step Up
A285
Selector 1 Step Mode
A286
Selector 1 Acknowledge
A288
Selector 1 Bit0
A28A
Selector 1 Bit1
A28C
Selector 1 Bit2
A28E
Selector 1 Bit Mode
A28F
Selector 1 Bit Acknowledge
A291
Selector 1 Power Up Mode
A292
Selector 1 Target
A293
Selector 1 Events
A294
Reserved (10 items)
A29E
...Repeated for Selector 2
Digital Counter (Read/Write Setting) (8 modules)
A300
Digital Counter 1 Function
A301
Digital Counter 1 Name
A307
Digital Counter 1 Units
A30A
Digital Counter 1 Block
A30C
Digital Counter 1 Up
A30E
Digital Counter 1 Down
A311
Digital Counter 1 Preset
A313
Digital Counter 1 Compare
A315
Digital Counter 1 Reset
A317
Digital Counter 1 Freeze/Reset
A319
Digital Counter 1 Freeze/Count
A31B
Digital Counter 1 Set To Preset
A31D
Reserved (11 items)
A328
...Repeated for Digital Counter 2
A350
...Repeated for Digital Counter 3
A378
...Repeated for Digital Counter 4
GE Multilin
RANGE
0 to 1000000
0 to 5
0 to 65535
0 to 1
0 to 1
0 to 3
0 to 999999.999
1 to 7
1 to 7
0 to 1
1 to 7
3 to 60
0 to 4294967295
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 1
0 to 4294967295
0 to 2
0 to 2
0 to 1
---
0 to 1
---
---
0 to 4294967295
0 to 4294967295
0 to 4294967295
–2147483647 to
2147483647
–2147483647 to
2147483647
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
---
F60 Feeder Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
s
0.001
F003
---
1
F167
---
1
F001
---
1
F102
---
1
F102
pu
0.001
F001
V
0.001
F060
---
1
F001
---
1
F001
---
1
F102
---
1
F001
s
0.1
F001
---
1
F300
---
1
F083
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F083
---
1
F300
---
1
F084
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
---
F205
---
---
F206
---
1
F300
---
1
F300
---
1
F300
---
1
F004
---
1
F004
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
---
F001
DEFAULT
100000
0 (SRC 1)
0
B
0 (Disabled)
0 (Disabled)
100
0
0
1
0 (Disabled)
7
50
0
0 (Time-out)
0
0
0
0
0 (Time-out)
0
0 (Restore)
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
"Counter 1"
(none)
0
0
0
0
0
0
0
0
0
0
B-55

Advertisement

Table of Contents
loading

Table of Contents